Danfoss VLT HVAC Drive FC 100 Operating Instructions Manual page 55

High power
Hide thumbs Also See for VLT HVAC Drive FC 100:
Table of Contents

Advertisement

®
VLT
HVAC DRIVE High Power
Operating Instruction
Size/Type
P315
P355
P400
P450
Table 3.7: E enclosures, 380-480 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/
110 Type T indicator fuses of the same size and amperage may be substituted for external use.
Danfoss PN
20220
20221
Table 3.8: Additional Fuses for Non-UL Applications, E enclosures, 380-480 V
Size/Type
P355
P400
P500
P560
Table 3.9: E enclosures, 525-600 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/
110 Type T indicator fuses of the same size and amperage may be substituted for external use.
Danfoss PN
20220
20221
Table 3.10: Additional Fuses for Non-UL ApplicationsE enclosures, 525-600 V
Suitable for use on a circuit capable of delivering not more than 100 000 rms symmetrical amperes,
500/600/690 Volts maximum when protected by the above fuses.
Circuit Breaker Tables
Circuit Breakers manufactured by General Electric, Cat. No. SKHA36AT0800, 600 Vac maximum,
with the rating plugs listed below can be used to meet UL requirements.
Size/Type
P110
P132
P160
P200
P250
Table 3.11: D enclosures, 380-480 V
Non UL compliance
If UL/cUL is not to be complied with, we recommend using the following fuses, which will ensure
compliance with EN50178:
In case of malfunction, not following the recommendation may result in unnecessary damage to
the frequency converter.
Bussmann PN*
Danfoss PN
170M5013
20221
170M6013
20221
170M6013
20221
170M6013
20221
Bussmann
170M4017
170M6013
Bussmann PN*
Danfoss PN
170M4017
20220
170M5013
170M4017
20220
170M5013
170M6013
20221
170M6013
20221
Bussmann
170M4017
170M6013
Rating plug catalog #
SRPK800A300
SRPK800A350
SRPK800A400
SRPK800A500
SRPK800A600
MG.11.F1.02 - VLT
®
is a registered Danfoss trademark
Rating
Losses (W)
900 A, 700 V
900 A, 700 V
900 A, 700 V
900A, 700 V
Ferraz
6.9URD31D08A0700
20 610 32.700
6.9URD33D08A0900
20 630 32.900
Rating
Losses (W)
700 A, 700 V
700 A, 700 V
900 A, 700 V
900 A, 700 V
Ferraz
6.9URD31D08A0700
20 610 32.700
6.9URD33D08A0900
20 630 32.900
3. How to Install
120
120
120
120
Siba
85
85
120
120
Siba
Amps
300
350
400
500
600
55
3