Emc Directive Related Standards - Mitsubishi Electric MELCEC Q Series User Manual

A mode
Table of Contents

Advertisement

8.
EMC AND LOW VOLTAGE DIRECTIVES
8.1.1

EMC Directive related standards

(1)
Standard
CISPR16-2-3
Radiated emission
EN61131-2:2007
CISPR16-2-1, CISPR16-1-2
Conducted emission
(2)
Standard
EN61000-4-2
Electrostatic discharge immunity
EN61000-4-3
Radiated, radio-frequency,
electromagnetic field immunity
EN61000-4-4
Electrical fast transient/burst
immunity
EN61000-4-5
Surge immunity
EN61131-2:2007
EN61000-4-6
Immunity to conducted
disturbances, induced by radio-
frequency fields
EN61000-4-8
Power-frequency magnetic field
immunity
EN61000-4-11
Voltage dips and interruption
immunity
Regulations regarding emission
Test item
*2
*2
*1
QP: Quasi-peak value, Mean: Average value
*2
Programmable controllers are open-type devices (devices designed to be housed inside other
equipment) and must be installed inside a conductive control panel. The corresponding tests
were conducted with the programmable controller installed inside a control panel.
Regulations regarding immunity
Test item
*1
*1
*1
*1
*1
*1
*1
*1
Programmable controllers are open-type devices (devices designed to be housed inside other
equipment) and must be installed inside a conductive control panel. The corresponding tests
were conducted with the programmable controller installed inside a control panel.
*2
The accuracy of an analog-digital converter module may temporary vary within
Test description
Radio waves from the product are
measured.
Noise from the product to the power
line is measured.
Test description
Immunity test in which electrostatic
is applied to the cabinet of the
equipment.
Immunity test in which electric fields
are irradiated to the product.
Immunity test in which burst noise is
applied to the power line and signal
line.
Immunity test in which lightning
surge is applied to the power line
and signal line.
Immunity test in which high
frequency noise is applied to the
power line and signal line.
Immunity test in which the product
is installed in inductive magnetic
field.
Immunity test in which power supply
voltage is momentarily interrupted.
8 - 2
Value specified in standard
• 30M-230MHz
QP: 40dB V/m (10m in
*1
measurement range)
• 230M-1000MHz
QP: 47dB V/m (10m in
measurement range)
• 150k-500kHz
*1
QP: 79dB, Mean: 66dB
• 500k-30MHz
QP: 73dB, Mean: 60dB
Value specified in standard
• 8kV Air discharge
• 4kV Contact discharge
80% AM modulation@1kHz
• 80M-1000MHz: 10V/m
• 1.4G-2.0GHz: 3V/m
• 2.0G-2.7GHz: 1V/m
• AC/DC main power, I/O power, AC
I/O (unshielded): 2kV
• DC I/O, analog, communication:
1kV
• AC power line, AC I/O power, AC I/
O (unshielded): 2kV CM, 1kV DM
• DC power line, DC I/O power: 0.5kV
CM, DM
• DC I/O, AC I/O (shielded), analog
communication: 1kV CM
0.15M-80MHz, 80% AM
modulation@1kHz, 10Vrms
50Hz/60Hz, 30A/m
• Apply at 0%, 0.5 cycles and zero-
cross point
• 0%, 250/300 cycles (50/60Hz)
• 40%, 10/12 cycles (50/60Hz)
• 70%, 25/30 cycles (50/60Hz)
10%.
*2
,

Hide quick links: