Mitsubishi Electric MELCEC Q Series User Manual page 49

A mode
Table of Contents

Advertisement

4.
CPU MODULE
Item
Comment
Expanded comment
Switch output mode from STOP to RUN
Self-diagnostics function
Operating mode when there is an error
Start-up method at RUN
Latch (power failure compensation) range
Remote RUN/PAUSE contacts
Print title entry
Keyword registration
I/O assignment
Step operation
Interrupt processing
Data link
Clock function
Allowable momentary power failure period
5VDC internal current consumption
Weight
External dimensions
Performance specifications (continued)
Q02CPU-A
Max. 4032 points (Set with the unit of 64 points)
Max. 3968 points (Set with the unit of 64 points)
Select "Set the output status at STOP to RUN. (Default)" or "Output after
Watchdog error supervision (watchdog timer fixed to 200ms)
Error detection in the memory, CPU, I/O, battery, etc.
(upon power supply on/power restoration after power failure, automatic restart by
turning the "RUN" switch of the CPU or on.)
(Possible to setup latch ranges for L, B, T, C, D, W)
Possible to setup one contact point for each of RUN/PAUSE from X0 to X1FFF.
Possible to register number of occupied I/O points and module model names.
Possible to execute or stop sequence program operations.
Possible to operate an interrupt program by the interrupt module or constant
Year, month, day, hour, minute, second, day of the week
Accuracy
Depending on the power supply modules
0.60A
98mm (H)
CAUTION
When the conventional system software packages and peripheral devices are
used, the usable device range are limited.
Details are provided in Section 2.2.3.
Model
Q02HCPU-A
operation execution."
Select STOP or continue
Initial start
L1000 to L2047 (default)
YES (128 characters)
YES
period interrupt signal.
MELSECNET/10, MELSECNET(II)/B
(automatic detection of the leap year)
• -3.18 to + 5.25s(TYP. + 2.12s)/d at 0
• -3.93 to + 5.25s(TYP. + 1.90s)/d at 25
• -14.69 to + 3.53s(TYP. - 3.67s)/d at 55
0.64A
0.20kg
27.4mm (W)
89.3mm (D)
4 - 3
Remark
Q06HCPU-A
Set in parameters.
Set in parameters.
Refer to Section 4.1.4
for details.
Set in parameters.
(refer to Section 4.2.1)
Range set by
parameters.
Set in parameters.
Set in parameters.
Set in parameters.
Refer to Section 4.3.
Refer to Section 5.1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qcpu-a seriesQ02cpu-aQ02hcpu-aQ06hcpu-a

Table of Contents