Standards relevant to the EMC directive

The standards relevant to the EMC Directive are listed in table below.
Certification
Test item
EN61000-6-4: 2007
CISPR16-2-3: 2010/A1: 2010
+A1: 2011
Radiated emission
EN61131-2: 2007
CISPR16-2-1: 2008/A1: 2010
(Power line)
CISPR22: 2008
(Electrical communication port)
Conducted emission
EN61000-6-2: 2005
EN61000-4-2: 2009
EN61131-2: 2007
Electrostatic discharge immunity
EN61000-4-3: 2006+A1: 2008
+A2: 2010
Radiated immunity
EN61000-4-4: 2012
Electrical fast transient/burst
(EFT/B) immunity
EN61000-4-5: 2006
Surge immunity
EN61000-4-6: 2009
Conducted immunity
EN61000-4-11: 2004
Short interruptions immunity
EN61000-4-11: 2004
Voltage dip
EN61131-2: 2007
EN61000-4-11: 2004
Voltage dip immunity
*1 This product is an open type device (a device designed to be housed inside other equipment) and must be installed inside a conductive
control panel. The corresponding test has been done with the programmable controller installed inside a control panel.
*2 QP : Quasi-peak value
*3 For the AC power supply line.
*4 For the electrical communication port.
*5 AV: Average value
Test details
Radio waves from the product are
*1
measured.
*3
Noise from the product to the power
line and electrical communication port
*4
is measured.
Immunity test in which electrostatic
discharge is applied to the product.
Immunity test in which electric fields
are radiated to the product.
*1
Immunity test in which burst noise is
applied to the power cable and signal
line.
Immunity test in which surge is applied
to the power line and signal line.
Immunity test in which high frequency
noise is applied to the power line and
signal line.
*3
Immunity test in which power supply
has short interruptions.
*3
Test in which voltage dip is applied to
the power supply.
*3
Immunity test in which voltage dip is
applied to the power supply.
Standard value
• 30M-230MHz
*2
QP
: 40dBV/m(10m (32.81ft.) in measurement
range)
• 230M-1000MHz
QP: 47dBV/m(10m (32.81ft.) in measurement range)
• 1GHz-6GHz
AV: 56dBV/m
PK: 76dBV/m
AC power line
• 0.15M-0.5MHz
QP: 79dBV
*5
AV
: 66dBV
• 0.5M-30MHz
QP: 73dBV
AV: 60dBV
Electrical communication port
• 0.15M-0.5MHz
QP, AV: Logarithmic decrease
• 0.5M-30MHz
QP: 87dBV
AV: 74dBV
• 8kV: 10 times at 1 second interval, Air discharge
• 4kV: 10 times at 1 second interval, Contact discharge
80%AM modulation @1kHz
• 80-1000MHz 10V/m
• 1400M-2000MHz 3V/m
• 2000M-2700MHz 1V/m
• AC power line: 2kV/5kHz
• DC power line: 2kV/5kHz
• I/O, communication line: 1kV/5kHz
AC power line
• Common mode: 2.0kV
• Differential mode:1.0kV
DC power line
• Common mode: 0.5kV
• Differential mode: 0.5kV
I/O, communication line
• Common mode: 1kV
0.15-80MHz, 80%AM modulation @1kHz, 10Vrms
0% of rated voltage, 250cycle
• 40% of rated voltage, 10cycle
• 70% of rated voltage, 25cycle
0% of rated voltage, 0.5cycle 20 times