APPENDICES
Number
Name
D9141
D9142
D9143
D9144
D9145
D9146
D9147
D9148
D9149
D9150
D9151
D9152
D9153
D9154
D9155
Number of
D9156
times of retry
D9157
execution
D9158
D9159
D9160
D9161
D9162
D9163
D9164
D9165
D9166
D9167
D9168
D9169
D9170
D9171
D9172
Table App.2.2 Special Register List (continued)
Description
• Stores the number of retries executed to I/O modules
or remote terminal modules which caused
communication error.
(Retry processing is executed the number of times set
at D9174.)
• Data becomes 0 when communication is restored to
normal.
• Station number setting of I/O modules and remote
terminal modules is as shown below.
Number of retries
• Retry counter uses 8 bits for one station.
b(n+7)
0/1
*
"n" is determined by station number of I/O module or
remote terminal module.
Odd number stations: b0 to b7 (n = 0)
Even number stations: b8 to b15 (n = 8)
Details
b15
to
b8
b7
D9141
Station 2
D9142
Station 4
D9143
Station 6
D9171
Station 62
Station 61
D9172
Station 64
Station 63
b(n+6) b(n+5) b(n+4) b(n+3) b(n+2) b(n+1) b(n+0)
Number of retries
0: Normal
1: Station error
App - 41
Applicable CPU
to
b0
Station 1
Station 3
Station 5
Usable with
A2C and A52G.