6.
BASE UNIT AND EXTENSION CABLE
6.3

Setting the Extension Stage Numbers

This section describes how to set the extension stage number for each of the extension
base units used.
Setting of the
stage number
setting connector
Loosen the upper and lower
screws of the base cover.
Remove the base cover from the
extension base unit.
Select the stage number from
1 to 7 in the connector (PIN1)
located between the extension
cable connectors IN and OUT.
Then, insert a connector pin into
the appropriate stage number.
Reattach the base cover to the
extension base unit and
fasten the screws.
(Tightening torque: 36 to 48N cm)
Completion
Stage number setting for extension base units
1st stage 2nd stage 3rd stage 4th stage 5th stage 6th stage 7th stage
POINT
(1) With the stage number setting connector, select one of the 1st to 7th that
matches to the extension stage number in ascending order.
(2) Do not assign the same stage number to several modules or skip any stage
numbers. Otherwise, improper I/O operation results.
Extension stage number setting
6 - 6
IN
OUT
PIN1
1
2
3
4
5
6
7