Which Are Not Compatible With Anu - Mitsubishi Electric MELCEC Q Series User Manual

A mode
Table of Contents

Advertisement

2.
SYSTEM CONFIGURATION
POINT
(1) Old software packages other than listed above cannot be used.
(2) To construct MELSECNET/10 network system with QCPU-A, use the AnU-
compatible GPP function software package (which includes "A4U" in its
programmable controller type name).
A network cannot be constructed with the GPP function software package
which is not compatible with AnU (which does not include "A4U" in its
programmable controller type name).
(3) Communication with GX Developer at 115.2kbps may not be available
depending on the peripheral devices. In such a case, select the lower
communication speed.
(4) When using Q02(H)CPU-A and conventional peripheral devices and setting
the programmable controller type as "A4U," designate the main program
setting to 28k steps or less with parameters. When "Main + parameter" is
written with the programmable controller with the setting of 29k steps or more,
"Cannot communicate with PC" is displayed, and writing to the CPU module is
disabled.
(5) Subprograms cannot be used with Q02(H)CPU-A. When using conventional
peripheral devices and setting the programmable controller type as "A4U," do
not specify any subprograms. If any subprograms are specified, "Cannot
communicate with PC" is displayed.
With Q06HCPU, subprogram 1 can be used, but subprograms 2 and 3
cannot.
When subprogram 2 or 3 is specified, the same message above is displayed.
2 - 5