Channel Configuration; Parameterizing Submodules - Siemens TX-I/O User Manual

Profinet bim v1.0
Hide thumbs Also See for TX-I/O:
Table of Contents

Advertisement

Mapping
Free subslots
Subslot 1
Numbering of the
module channels
Multistate
output channels
Procedure
Properties
dialog box
20 / 94
Siemens
Building Technologies
3.3.2

Channel Configuration

The functionality of the channels of the TX-I/O modules is
mapped to the input/output submodules. The supported
submodules (2) are listed in the hardware catalog under
each TX-I/O module (1).
Submodules can be inserted in any free subslot (free subslots are marked in
green).
Subslot 1 of the modules is defined at the factory with an object that is typical for
the corresponding module. The subslot contains
the binary I/O process data of the configured binary I/O channels and
the override information of configured output channels.
Module channels begin with subslot number 2 for the first I/O channel and end with
the subslot number of the maximum number of module channels + 1.
Multistate output channels (MO) must be carefully connected.
The channels must be integrated in precisely the order in which they appear in
the catalog.
1.
Hardware catalog: open the module with the affected objects
2.
Enter the required objects in the TX-I/O module in the rack in the correct
order by drag&drop.
This only works with individual objects – multiselection is not possible.
3.
Save
3.3.3

Parameterizing Submodules

The functions with subslots of connected TX-I/O modules can be parameterized in
the corresponding properties dialog box. The dialog box is opened by
doubleclicking on the submodule.
Parameterized values are transferred to the controller during loading of the project.
The controller sends the parameter values to the Profinet BIM only during the
Profinet communication start. After communication has started, the channel
TX-I/O PROFINET BIM V1.0
Engineering
CM110564en_02
23.09.2010

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents