Diagnostics; Diagnostics With The Simatic Manager; Basic Diagnostics; Advanced Diagnostics - Siemens TX-I/O User Manual

Profinet bim v1.0
Hide thumbs Also See for TX-I/O:
Table of Contents

Advertisement

Step-by-step procedure
Version and MLFB
(order number)
Serial number
Ethernet port statistics
62 / 94
Siemens
Building Technologies
5

Diagnostics

5.1

Diagnostics with the SIMATIC Manager

Identification-related diagnostics are used to diagnose the Profinet BIM.
The function block DIAG-DESIGO-IO is provided in the Emx to evaluate the
diagnostics data with the SICLIMAT X environment.
5.1.1

Basic Diagnostics

The following diagnostics information is displayed in the module information window:
 the firmware version
 the hardware version
 MLFB number (machine-readable production number = order number)
 Ethernet port statistics
1.
SIMATIC Manager, left screen section: Mark CPU > menu: Target system >
Show accessible nodes
Opens the Accessible Nodes dialog box
2.
General tab, group field: Version > Version
3.
Identification tab, group field: Manufacturer information > Serial number
4.
Statistics tab
5.
Close button.
Closes the dialog box.
5.1.2

Advanced Diagnostics

TX-I/O PROFINET BIM V1.0
Diagnostics
CM110564en_02
23.09.2010