Definition, addition
Definition, addition
Definition, addition
Definition, addition
Definition, addition
Switching behavior
46 / 94
Siemens
Building Technologies
4.9.1
Backup Mode
Function for control of the behavior of the function when changing to the
'MasterDown' status.
Possible values
Description
NO
Process value = INACTIVE, 0 (Off)
VALUE
Specific value of the parameter [BOBackupValue]
KEEP
Save the last active process value
4.9.2
MO Backup Value
Parameter – type [BinaryValueEnum] – that represents the backup value and
becomes valid in the following cases:
a change in status to 'MasterDown' and
the parameter [BackupMode] = VALUE
Possible values
Description
ACTIVE
Binary output is active.
INACTIVE
Binary output is inactive.
Backup values are the same values as the process data values for the channels.
For information, refer to 'Process Data Channel Mapping' of each TX-I/O module
with MO function.
4.9.3
Minimum OFF Time
Parameter for defining the minimum pulse length for the OFF channel (first
channel).
Value range
Unit
1...255
0.1 s
4.9.4
Pulse Time
Parameter for defining the pulse length for contact channels (2...n).
Value range
Unit
1...255
0.1 s
4.9.5
Enabling Local Override
Parameter for enabling/disabling the module key Up/Down for the 'Local override'
function.
General switching behavior (for enabled local overriding):
Switch from automatic to local override (manual):
The current process value is valid until a new manual command is issued.
TX-I/O PROFINET BIM V1.0
Parameters
CM110564en_02
23.09.2010