Before you start
Procedure
Siemens
Building Technologies
 Up to 64 TX-I/O modules can be connected with a Profinet BIM at the same
time.
3.3.1

Module Configuration

The TX-I/O modules supported by the Profinet BIM are found in the hardware
catalog under the TXB1.Profinet submodule.
Please observe the following points when working on the module configuration:
Recommendation: Keep the addresses identical with the parameterized
SIMATIC input and output addresses.
---> TX-I/O module addresses must agree with the number of the slot in which
they are located and
---> TX-I/O modules must be inserted in the slot whose number matches
the corresponding TX-I/O module address.
Slots suitable for accepting TX-I/O modules are marked in green.
A TX-I/O module can be deleted at any time with the Del button. In doing so, you
must reply to a security prompt (example for a TXM1.6R module):
1.
Upper window section: click the required submodule
Opens the TX-I/O module in the lower window section.
2.
Hardware catalog: insert the required TX-I/O module by drag&drop.
When dragging the object, the free slots are displayed in green. After
dropping the module, a window similar to the one shown below appears
(extract, with TXM1.6R as an example).
3.
Save
We recommend saving at meaningful intervals, but always for each
inserted TX-I/O module.
TX-I/O PROFINET BIM V1.0
Engineering
19 / 94
CM110564en_02