Engineering The Profinet Bim With The Simatic Manager - Siemens TX-I/O User Manual

Profinet bim v1.0
Hide thumbs Also See for TX-I/O:
Table of Contents

Advertisement

Supported TX-I/O
modules
Supported slots
18 / 94
Siemens
Building Technologies
6.
Import Profinet BIM to the Profinet network by drag&drop of the
TXB1.Profinet BIM.
After releasing the mouse button, the Profinet BIM is inserted and is displayed
in the Profinet network.
Note
When clicking the Profinet BIM, the slot allocation and I/O addresses are
displayed in detail in the station window.
7.
Rightclick I/O bar > context menu: Object Properties
Opens the PROFINET I/O system properties dialog field.
8.
Update time tab: mark the device > Edit button
Opens the Edit update time/mode dialog field.
9.
Set the update time to 256 ms using the dropdown list box.
This is a recommendation. A higher clock rate makes no sense since the
island bus is clocked at 512 ms.
10. Close with OK.
3.3
Engineering the Profinet BIM with the
SIMATIC Manager
The Profinet BIM is a modular device. It supports specific TX-I/O modules and their
corresponding channel functions.
TXM1.8D
TXM1.8U
TXM1.16D
TXM1.8U-ML
The following sections explain the engineering procedure in terms of
 module configuration
 submodule configuration and
 parameterization.
 Profinet BIM supports 120 slots. TX-I/O modules can be inserted in any slot
within this range (1...120).
TX-I/O PROFINET BIM V1.0
Engineering
TXM1.8X
TXM1.6R
TXM1.8X-ML
TXM1.6R-M
TXM1.6RL
TXM1.8P
CM110564en_02
23.09.2010

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents