Definition, addition
Parameter
Definition, addition
Mapping for
multicolored LEDs
Only modules TXM1.8D
and TXM1.6R-M
28 / 94
Siemens
Building Technologies
4.2.3
Debounce Time
Parameter to define the minimum time that the input signal must remain stable in
order to be valid.
Changing the parameter resets an active debounce timer.
Value range
Unit
0..255
0.1 s
4.2.4
Display
Parameters for color definition of the meaning of an indication.
As a result, a specific LED color is assigned to each meaning.
Parameter type: [DisplayEnum]
Possible values
Description
Normal
LED is lit green
Alarm
LED is lit red
Service
LED is lit yellow
Note
This parameter is used to assign a LED color to a signal type. After the
configuration, the color remains permanently assigned.
It is expressly not intended for use in combination with the status of the process
value.
4.2.5
Process Data
For process data mapping of binary input functions to channel process data, refer
to the corresponding sections in Chapter 4, "Process Data Channel Mapping" of
the TX-I/O modules.
4.2.6
Channel Diagnosis
Alarm type
Cause / solution
Invalid
Check the module configuration and parameterization
TX-I/O PROFINET BIM V1.0
Parameters
CM110564en_02
23.09.2010