Channel Diagnosis - Siemens TX-I/O User Manual

Profinet bim v1.0
Hide thumbs Also See for TX-I/O:
Table of Contents

Advertisement

Current output
(4 mA...20 mA)
Siemens
Building Technologies
SIMATIC value
Decimal
Hex
20736
5100
1
1
0
0
-1
FFFF
-141
-32767...-142
-32768
SIMATIC value
Decimal
Hex
32767
7FFF
32512
7F00
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
-20736
E500
-27648
E4FF
-32512
8100
-32513
80FF

4.11.8 Channel Diagnosis

Alarm type
Cause / solution
Invalid
Check the module configuration and parameterization
No_Output
Operating voltage too low -> check the power
Over_Range
Sensor shows a higher value than the rated range > check the output process
value
Under_Range
Sensor shows a lower value than the rated range > check the output process
value
Short_Loop
The connection between the sensor and module shows a value that indicates a
short-circuit > check the sensor and cable connection between the sensor
and module
Open_Loop
The connection between the sensor and module shows a value that indicates an
interruption (open loop) > check the sensor and cable connection between
the module and field device
Unreliable
The operating voltage ACDC 24 V is below a specific value (AC or DC) > check the
operating voltage value (power supply)
TX-I/O PROFINET BIM V1.0
Parameters
Analog value
Description
7.5 V
361.7 µV
0 V
361.7 µV
Underflow, not supported
Output value limited to 0 V
-54 mV
Underflow, not supported
0.00V
Output value limited to 0 V
Channel diagnosis: Under_Range
Analog value
Description
0.00 mA
Overflow, operating voltage off
22.81 mA
Overshoot range
20 mA
15 mA
Measurement range
4mA  578.7 nA
4 mA
Underflow range
Not supported, output value limited to
0 mA
0 mA
Underflow, no voltage/no current
55 / 94
CM110564en_02
23.09.2010