Updating The S7 Hardware Configuration - Siemens TX-I/O User Manual

Profinet bim v1.0
Hide thumbs Also See for TX-I/O:
Table of Contents

Advertisement

Requirements
Step-by-step procedure
72 / 94
Siemens
Building Technologies
6.2.4

Updating the S7 Hardware Configuration

It is assumed that the reader knows of the procedure implemented above. The
following steps are therefore repeated in concise form.
1
Start the S7 hardware configurator (if this is not already the case)
2
Station > Import
Opens the Import dialog box.
3
Import dialog box: mark the modified GSDML file > click Open
4
Answer various security queries accordingly.
Example:
Two options of acknowledgement are possible:
Yes
Acknowledgement for one object (i.e., a security prompt will be
displayed for the next object).
All
Acknowledgement for each category of objects; in this way, for
example, all racks, all subsystems etc. can be handled with one
security query in each case.
5
Reply to the security query by clicking Yes.
The data is then saved and the dialog box closes.
6
Reengineer all previously removed modules and submodules.
These are modules and submodules that were previously removed from the
HW configuration because they had been changed.
7
Station > Save and compile
This action saves and compiles the module and submodule data.
8
Target system > load to module
Opens the 'Select target module' dialog box
9
Select target module > click OK
Follow the dialog; the action ends after a short time.
TX-I/O PROFINET BIM V1.0
Updates
CM110564en_02
23.09.2010