Binary Input (Static)

BI_STATIC (SIMATIC Manager hardware catalog)
Static binary input = input for detecting/processing static status changes in applied
signals.
A floating contact is connected with the static binary input. The object carries out a
cyclical check at the input. Every change from one stable status to the other is
detected.
4.1.1

Contact

Parameters for defining the contact type.
Possible values
Description
NO Contact
"Not Open" contact
NC Contact
"Not Closed" contact
Status
NO contact
Contact position
LED
indication
Closed
LED on
Open
LED off
4.1.2

Debounce Time

Parameter to define the minimum time that the input signal must remain stable in
order to be valid.
Changing the parameter resets an active debounce timer.
Value range
Unit
0..255
0.1 s
4.1.3

Display

Parameters for color definition of the meaning of an indication.
As a result, a specific LED color is assigned to each meaning.
Parameter type: [DisplayEnum]
Possible values
Description
Normal
LED is lit green
Alarm
LED is lit red
Service
LED is lit yellow
Note
 This parameter is used to assign a LED color to a signal type. After the
configuration, the color remains permanently assigned.
TX-I/O PROFINET BIM V1.0
Parameters
NC contact
Process
LED
value
indication
1
LED off
0
LED on
Process
value
0
1
25 / 94
CM110564en_02
23.09.2010