Preparation
Passwords
Step-by-step procedure
68 / 94
Siemens
Building Technologies
6

Updates

6.1

Firmware Update

6.1.1

FW Upload to TX-I/O BIM

1
Download the zip file pnbim firmware Vxxx.zip and the GSDML file (.xml) from
Swanweb
The following link is an example and is neither binding nor complete (you
need to navigate further, but this is self-explanatory)
https://intranet.sbt.siemens.com/swanlink/default.php?tabcard=4b73a4b5&src
=txio/asn/TXB1.Profinet
2
Extract the file pnbim_fw_V0_2_xx.bin and copy it together with the GSDML
file to a local folder – e.g., C:\temp.
Passwords are required below during the login procedure.
User name
Password
guest
guest01
user
user01
root
root
1
Start > Run
2
Enter cmd in the text box and then return key
Opens the DOS commander
3
Optional (recommended): navigate to the folder named above (e.g., C:\temp)
with cd c:\temp > return key
4
At the DOS prompt (C:\temp>) enter: ftp > return key
Prompts ftp>
5
At the DOS prompt (ftp>) enter the IP address of the TX-I/O BIM:
open xxx.xxx.xxx.xxx > return key
Displays 'Connected to <IP address> and 220 Service ready'
6
At the DOS prompt User (<IP address>: (none)) enter: user > return key
Display '331 User name ok, need password'
7
At the DOS prompt (password:) enter (hidden text input): user01 > return key
Displays '230 User logged in'
8
At the DOS prompt (ftp>) enter:
put pnbim_fw_Vx_x_xx.bin > return key
Displays '200 Command OK, 150 Connecting for STOR, 226 Transfer OK,
Closing connection' and 'ftp: xxxxxx bytes sent in xxx.xx Seconds
xx.xxKbytes/s.'
9
At the DOS prompt (ftp>) enter: quit > return key
Exits ftp
TX-I/O PROFINET BIM V1.0