Diagnostics On Profinet Bim; Diagnostics In Telnet; Telnet Commands - Siemens TX-I/O User Manual

Profinet bim v1.0
Hide thumbs Also See for TX-I/O:
Table of Contents

Advertisement

64 / 94
Siemens
Building Technologies
5.2

Diagnostics on Profinet BIM

LED indication
on
off
on
flashing
on
on
flashing
flashing
flashing
off
flashing
on
off
on
on
5.3

Diagnostics in Telnet

5.3.1

Telnet Commands

The following commands are used on the DOS command level for working with
Telnet:
help firmware
Command
Description
fwupdate
Starts firmware update
cimiupdate
Starts CIMI firmware update
cfgget
Get device configuration
cfgupdate
Update device configuration
calibrate
Starts CIMI calibration
devicestop
Stops Profinet IO Device
devicestart
Starts Profinet IO Device
setPvMode
Sets ComMode of a device
to Master/Slave or Frontend/Backend
help info
Command
Description
devicelist
Shows the device and module list
alarmlist
Shows the active alarms
diagbasic
Display the diagnostic and process
alarms
diagextended
Display the extended diagnosis
ethstats
Display the ethernet statistics
showlog
Display trace log
version
Display the firmware version
TX-I/O PROFINET BIM V1.0
Diagnostics
on
flickerin
g
flickerin
g
Description
Cause
Firmware runs without faults
Alarm present
Firmware is running, no Profinet
communication
Hardware problem
Firmware update is running, firmware is
running
Firmware update is running, firmware is
not running
Firmware is not running
Connection to Ethernet port 1 available
Connection to Ethernet port 2 available
Ethernet communication on port 1
Ethernet communication on port 2
CM110564en_02