MissedCnt
Value
Meaning
0xyyyy
Number of telegrams that have not returned in time for the start of the task. This value should
remain almost constant. If the value keeps rising, the task time should be lengthened.
UDP/IP diagnosis
BoxState
Value
Meaning
0x0000
No error
0x0001
No current inputs
0x0002
Outputs are written as zero
0xxxzz
xx - warning level. The value here is incremented by one each time the data is not received in
time. When data is exchanged correctly, the value is decremented by one. When the maximum
warning level (default value 100) is reached, zero is written to the output data, and it is only
enabled again for the normal process image when the warning level has reached zero.
MissedCnt
Value
Meaning
0xyyyy
Number of telegrams that have not returned in time for the start of the task. This value should
remain almost constant. If the value keeps rising, the task time should be lengthened.
8.4
ModbusTCP diagnostic
• See Modbus diagnostic function [} 71]
• See ModbusTCP error answers [} 67]
BC9000 and BC9100
Version: 4.0.0
Error handling and diagnosis
83