7.6.1.3
Register settings, Table 100
The registers can be set through a dialog using the KS2000 configuration software, or it is possible to write
into the registers directly.
Register Description
0-1
IP address
2-3
IP mask
4-13
Device Name
14
Watchdog AMS/ADS
15.0
0
enable ModbusTCP
bin
1
disable ModbusTCP
bin
15.1
0
enable AMS/ADS
bin
1
disable AMS/ADS
bin
16.8
0
Ethernet mode half duplex
bin
1
Ethernet mode full duplex
bin
16.12
0
Autobaud off
bin
1
Autobaud on
bin
16.13
0
10 Mbaud
bin
1
100 Mbaud
bin
17-18
Default Gateway
24
Watchdog ModbusTCP
25.0
Entry of a fieldbus error (connection to switch
interrupted) in the flags area diagnosis [} 39]
0
Error was not entered
1
Error was entered
26
ModbusTCP port no.
27
ADS connection service life
28
Modbus connection service life
29.0
ModbusTCP mode
1
Fast ModbusTCP
bin
BC9000 and BC9100
Default
0xAC, 0x10, 0x11,
0x00
0xFF, 0xFF, 0x00,
0x00
BC9000
1000 ms
0
bin
0
bin
1
bin
1
bin
1
bin
0x00, 0x00, 0x00,
0x00
1000 ms
0
bin
502
10 s
10 s
0
bin
Version: 4.0.0
Fieldbus system
Bus Terminal Controller
BC9000, BC9100,
BK9000, BK9050,
BK9100
BC9000, BC9100,
BK9000, BK9050,
BK9100
BC9000, BC9100,
BK9000, BK9050,
BK9100
BC9000, BC9100,
BK9000, BK9050,
BK9100
BC9000, BC9100,
BK9000, BK9050,
BK9100
BC9000, BC9100,
BK9000, BK9050,
BK9100
BC9000, BC9100,
BK9000, BK9050,
BK9100
BC9000, BC9100,
BK9000, BK9050,
BK9100
BC9000, BC9100
BC9000, BC9100,
BK9000, BK9050,
BK9100
BC9000, BC9100,
BK9000, BK9050,
BK9100
BC9000, BC9100,
BK9000, BK9050,
BK9100
BC9000, BC9100,
BK9000, BK9050,
BK9100
77