AdsServerAdsStateB7
Data type (read only)
String
AdsServerDeviceStateB7
Data type (read only)
INT
AdsServerTypeB7
Data type (read only)
String
ADSWriteControlBA
Data type (write only)
NetID
Port
ADSSTATE
DEVSTATE
LEN
SRCADDR
WRITE
TMOUT
Acyclic data communication
With acyclic data communication it is important to note that about 20 to 30 ms are required in order
to establish a TCP/IP connection. Following the successful establishment of a connection the ADS
data are sent or read. An ADS read of 1000 bytes takes about 50 ms. If no data are transmitted for
10 seconds, the TCP/IP connection is disconnected from the BC/BK9000, B/C900.
Register port 100
The ADS port number in the BK/BC9000, B/C900 for register communication is fixed, being set at 100.
Index group
Index offset (value range)
Hi-Word
0
0...127
1...64
0...3
Timeout of the ADS function block
When reading the register, the time out of the ADS block has to be set to a time longer than 1 sec-
ond.
BC9000 and BC9100
Meaning
Start - the local PLC is running
Start - the local PLC is stopped
Meaning
0 - Start - the local PLC is running
1 - Stop - the local PLC is stopped
Meaning
Coupler_PLC
Meaning
Net ID of the BC9000,C900
800
5 - RUN / 6 - STOP
0
0
0
rising edge starts the block
example: t#1000 ms
Meaning
Lo-Word
0...255
Registers in the Bus Coupler
Hi-Word, table number of the Bus Coupler
Lo-Word, register number of the table
1...64
Register of the Bus Terminals
Hi-Word, channel number
Lo-Word, register number of the Bus Terminal
Version: 4.0.0
Fieldbus system
57