Examples For Modbustcp - Beckhoff BC9000 Documentation

Bus terminal controller for ethernet
Table of Contents

Advertisement

Fieldbus system
Here the offset always describes a word. Offset 0x0003 writes to the fourth word in the output process
image. The length indicates the number of words, and the Byte count is formed from the combination of all
the bytes that are to be written. Sample: 4 words - correspond to a byte count of 8
The data bytes contain the values for the analog outputs. In this example, two words are to be written. The
first word is to receive the value 0x3FFF, and the second word is to receive the value 0x7FFF.
Query
Byte name
Function code
Read start address high
Read start address low
Read length high
Read length low
Write start address high
Write start address low
Write length high
Write length low
Byte count
Data 1 high
Data 1 low
Data 2 high
Data 2 low
Response
The coupler replies with the start address and the length of the bytes to be transferred in Byte count. The
data information follows. In this example the first word contains 0x0038 while the second word contains
0x3F0B.
Byte name
Function code
Byte count
Data 1 high
Data 1 low
Data 2 high
Data 2 low
7.5.5

Examples for ModbusTCP

Examples for Modbus TCP are contained in this help text.
Simple example: Modbus TCP via VB6.0 https://infosys.beckhoff.com/content/1033/bc9000/Resources/
zip/4351427467.zip
Example: ModbusTCP via VB6.0, set and reset of the watchdog:https://infosys.beckhoff.com/content/1033/
bc9000/Resources/zip/4351429643.zip
74
Sample
23
0
0
0
2
8
0
0
2
4
63
255
127
255
Sample
23
4
0
56
63
11