Technical Data; Fig. 2 Bc9000 And Bc9100 - Beckhoff BC9000 Documentation

Bus terminal controller for ethernet
Table of Contents

Advertisement

Product overview
outputs return in the inactive state. The timeout periods for the Bus Couplers correspond to the usual
settings for the fieldbus system. When converting to a different bus system it is necessary to bear in mind the
need to change the timeout periods if the bus cycle time is longer.
The interfaces
A Bus Coupler has six different methods of connection. These interfaces are designed as plug connectors
and as spring-loaded terminals.
2.3

Technical data

Fig. 2: BC9000 and BC9100
System data
Number of I/O modules
Number of I/O points
Data transfer medium
Distance between
modules
Data transfer rate
Topology
10
Ethernet (BC9000)
only limited by the IP address space
depending on controller
4 x 2 twisted-pair copper cables; category 3 (10 Mbit/s), category 5 (100 Mbit/s)
100 m (distributor hub to BC9000)
10 / 100 Mbit/s
star wiring
Version: 4.0.0
Ethernet (BC9100)
Line: max. 100 m between two BC9100
star wiring, up to 20 BC9100 in one line
BC9000 and BC9100