Fieldbus system
Fig. 42: Displaying the AMS routing table using the KS2000 configuration software
Entering values in the routing table via ADS
The AMS routing table can be loaded into the BC9000 via ADS. Ensure that the first entry is that of the
sender, since this setting becomes effective immediately and may otherwise prevent further entries in the
AMS routing table.
Download (https://infosys.beckhoff.com/content/1033/bc9000/Resources/zip/6744240267.zip)
7.4.3.3.2 Example communication between BC9000s
ADS-Communication
Data can be sent directly to another BC9000 using the ADS function blocks from the TcADSBC.lb6 library.
ADSREADEX can be used to read data from another BC9000, ADSWRITE can be used for writing. A
maximum of 3 BC9000 can be accessed at the same time. In order to communicate with further BC9000s,
the connection to at least one BC9000 has to be closed via ADSCLOSE. Make sure that only a maximum of
3 connections to a BC9000 exist (the 4th connection should be reserved for programming). These
connections may also be established by another remote station.