Mapping The Bus Terminals; Local Process Image; Fig. 26 Assign Bus Terminals To The Higher Level Controller - Beckhoff BC9000 Documentation

Bus terminal controller for ethernet
Table of Contents

Advertisement

Programming
Fig. 26: Assign bus terminals to the higher level controller
Remember that none of the process images in use may be larger than 512 bytes.
6.4

Mapping the Bus Terminals

The precise assignment of the byte-oriented Bus Terminals may be found in the configuration guide for the
particular bus terminal. This documentation is available on the Beckhoff Products & Solutions CD or on the
Internet under http://www.beckhoff.de.
Byte oriented Bus Terminals
KL15x1
KL25xx
KL3xxx
KL4xxx
KL5xxx
KL6xxx
KL7xxx
KL8xxx
6.5

Local process image

All connected bus terminals are assigned in the default setting to the local process image of the BC/BX.
Mapping within the Bus Terminal Controller is carried out according to the following rule:
First come all the complex Bus Terminals, in whatever sequence they are physically inserted, followed by the
digital Bus Terminals which are padded to a whole byte.
The default mapping of the complex Bus Terminals is:
• complete evaluation
• Intel format
• Word alignment
38
Bit oriented Bus Terminals
KL10xx, KL11xx, KL12xx, KL17xx, KM1xxx
KL20xx, KL21xx, KL22xx, KL26xx, KL27xx, KM2xxx
KL9110, KL9160, KL9210, KL9260
Version: 4.0.0
BC9000 and BC9100