Calendar override
Note
The calendar override can be set from 0 (OFF) to 99 days.
Note
In case no regeneration occurred during this programmed interval of day (calendar
override), the controller will automatically start a regeneration.
Note
This type of regeneration is carried out at the regeneration time even on non-enabled days.
Note
This option is displayed only if SH (regeneration mode) is set to 1, to 2 or to 4.
Set the calendar override.
A
Use
and
to set the calendar override.
B
Press
to validate and switch to the next parameter.
Main electrical frequency
Set the main electrical frequency to 50 or 60 Hz.
A
Use
and
to set the frequency.
B
Press
to validate and switch to the next parameter.
Manual opening of brine valve
Note
During the opening and the closure of the brine valve, a mechanical movement appears on
the display. When the valve is completely open, the display shows bMON and when the valve
is completely closed, the display shows bMOF.
Caution
When this command is operated, the brine valve is under full control of the user/installer.
Warning
Pentair is not responsible for any damage caused by the incorrect use of this command by
the user/installer.
A
Press
to open the brine valve.
B
Press
to close the brine valve.
C
Press
to validate and switch to the next parameter.
Ref. MKT-IM-009 / C - 08.06.2018
Installer Manual Siata V132-SFE-EV-VIRIDION - Programming
59 / 110