Installer Manual Siata V132-SFE-EV-VIRIDION - Installation
Length of connection pipes between valve and lower distribution system
The riser tube (distributor) must be cut between 12 to 17 mm, measured from the upper edge of the
tank. Remove the sharp edges (1 mm x 45°) to avoid damage to the seal during installation. See
drawing below.
Note
The riser tube (distributor) must be ISO PN 10 or higher standard:
minimum height 12 mm;
maximum height 17 mm;
chamfer 1 mm x 45°;
ISO PN10 or higher pipe.
Distributor tube
36 / 110