BEST ACCESS SYSTEMS W Series Service Manual page 210

Table of Contents

Advertisement

Installation Instructions for 83KW/93KW–85KW/95KW IDH Max Cylindrical Locks
Set DIP
switches.
Figure 24 Setting DIP switches
Setting DIP switches
Feature
Reader LED input configuration
Provides the ability to select between one-wire and two-wire LED
operation for the reader LED input.
Baud rate selection
Provides the ability to select the baud rate for communication between the
panel interface circuit board and the lock's control electronics circuit board.
Note: To control the baud rate using DIP switches 2 and 3 on the panel
interface circuit board, DIP switches 6 and 7 on the control electronics circuit
board both must be set to ON (automatic baud rate detection).
Request-to-exit (RQE) status output configuration
Provides the ability to invert the request-to-exit (RQE) status signal. If DIP
switch 4 is ON, the contact is closed when the door knob/lever is turned,
activating the RQE switch.
Door status output configuration
Provides the ability to invert the signal for the door status output. If DIP
switch 5 is ON, the contact is closed when the door is closed (the door
status switch is closed).
Communication tamper configuration
Provides the ability to invert the signal for the communication tamper
output. If DIP switch 6 is ON, the contact is closed when the
communication connection between the panel interface circuit board and
the lock's control electronics circuit board is OK.
Sounder input configuration
Provides the ability to invert the interpretation of the sounder input signal.
The normal input configuration interprets a closed contact as sounder ON.
22
Installing the panel interface module
25
59
26
1 Make sure that the output voltage of the power supply
2 Make the final power supply connections.
3 Adjust the power supply output voltage to
BEST ACCESS SYSTEMS
Indianapolis, Indiana
Set panel interface module
DIP switches
Set the DIP switches on the panel interface circuit
board. Refer to the table below. Default settings are
shown in boldface.
Note: DIP switch 8 is used in IDH Max Mortise
installations. Leave this switch set to ON.
Set and connect power supply
for the panel interface module and lock is set to
15 volts DC or lower.
13.8 volts DC.
Option
DIP Switch Setting
Two-wire operation
Switch 1–ON
One-wire operation
Switch 1–OFF
38400 bps
Switch 2–OFF Switch 3–OFF
19200 bps
Switch 2–ON Switch 3–OFF
9600 bps
Switch 2–OFF Switch 3–ON
2400 bps
Switch 2–ON Switch 3–ON
Normally-open (NO)
Switch 4–ON
Normally-closed (NC)
Switch 4–OFF
Normally-closed (NC) Switch 5–ON
Normally-open (NO)
Switch 5–OFF
Normally-closed (NC) Switch 6–ON
Normally-open (NO)
Switch 6–OFF
Normal input
Switch 7–ON
Inverted input
Switch 7–OFF

Advertisement

Table of Contents
loading

This manual is also suitable for:

35hw83kw93kw34hw85kw95kw ... Show all

Table of Contents