BEST ACCESS SYSTEMS W Series Service Manual page 183

Table of Contents

Advertisement

Installing the panel interface module
23
Connect panel interface module to
access control panel/reader interface
With power removed from the panel interface circuit
board and the access control panel/reader interface,
connect the wiring between the panel interface circuit
board and the access control panel. Refer to the table
below.
Connecting to the access control panel/reader interface
Terminals
TPR (on J3)
Communication tamper
output or
Latchbolt status output
DLS (on J3)
Door status & latchbolt
status output or
Door status output
RQE (on J3)
Request-to-exit status
output
STK (on J3)
Strike input
continued
Installation Instructions for 34HW–35HW IDH Max Mortise Locks
Installation Instructions for 34HW–35HW IDH Max Mortise Locks
Description
Switch-like output to the access control panel/reader interface that is
configured using DIP switch 8 to serve one of two possible functions:
Option 1—Communication tamper output: Indicates the status of the
communication connection between the panel interface circuit board and the
lock's control electronics circuit board. By default, the output is closed to
indicate communication is OK and open to indicate communication has been
interrupted.
Option 2—Latchbolt status output: Indicates the state of the lock's
latchbolt status switch. By default, the output is closed to indicate the latchbolt
status switch is closed.
Note: The lock's latchbolt status switch is closed when the latchbolt is extended.
Switch-like output to the access control panel/reader interface that is
configured using DIP switch 8 to serve one of two possible functions:
Option 1—Door status & latchbolt status output: Indicates whether the
door is secure (both the door status and latchbolt status switches are closed) or
unsecure (one or both of these switches are open). By default, the output is
closed to indicate the door is secure.
Option 2—Door status output: Indicates the state of the lock's door status
switch. By default, the output is closed to indicate the door status switch is
closed.
Note: The lock's door status switch is closed when the door is closed.
Switch-like output to the access control panel/reader interface that indicates
the status of the lock's RQE switch. By default, the output is closed to indicate
the RQE switch is closed.
Note: The lock's RQE switch is closed when the door knob/lever is turned,
activating the switch.
Input from the access control panel's/reader interface's strike relay, which
provides the solenoid control signal. The access control panel/reader interface
output usually has normally open (NO) and normally closed (NC) terminals, as
well as a common terminal. The common and NO terminals should be
connected to the two STK terminals on J3. To invert the operation, use the
access control panel's/reader interface's common and NC terminals.
The operation of the solenoid varies by lock function. See the W Series Service
Manual (T60775).
BEST ACCESS SYSTEMS
Indianapolis, Indiana
J3
TPR
DLS
Connect to access control panel/reader interface.
Figure 22a Connecting to the access control panel/
reader interface
RQE
STK
Related DIP switches
DIP switch 8
configures the function
of this output.
DIP switch 6 provides
the ability to invert the
signal.
DIP switch 8
configures the function
of this output.
DIP switch 5 provides
the ability to invert the
signal.
DIP switch 4 provides
the ability to invert the
signal.
None
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

35hw83kw93kw34hw85kw95kw ... Show all

Table of Contents