Summary of Contents for Siemens SIMATIC S7-1500

  • Page 2 Digital output module DQ 16x230VAC/1A ST Triac (6ES7522-5FH00-0AB0) Preface Documentation guide SIMATIC Product overview Wiring S7-1500/ET 200MP Digital output module Parameters/address space DQ 16x230VAC/1A ST Triac (6ES7522-5FH00-0AB0) Diagnostic alarms Equipment Manual Technical specifications Dimensional drawing Parameter data records 12/2021 A5E34934069-AC...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Purpose of the documentation This manual supplements the system manual S7-1500/ET 200MP (https://support.industry.siemens.com/cs/ww/en/view/59191792). Functions that relate in general to the systems are described in this system manual. The information provided in this manual and in the system/function manuals supports you in commissioning the systems.
  • Page 5 Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 6: Table Of Contents

    Table of contents Preface ..............................3 Documentation guide ..........................6 Product overview ........................... 8 Properties ..........................8 Functions .......................... 10 2.2.1 Switching cycle counter ..................... 10 Wiring ..............................12 Parameters/address space ........................13 Parameters ........................13 Declaration of parameters ....................14 Address space ........................
  • Page 7: Documentation Guide

    This arrangement enables you to access the specific content you require. Basic information The System Manual and Getting Started describe in detail the configuration, installation, wiring and commissioning of the SIMATIC S7-1500 and ET 200MP systems. The STEP 7 online help supports you in the configuration and programming. Device information Product manuals contain a compact description of the module-specific information, such as properties, wiring diagrams, characteristics and technical specifications.
  • Page 8 Documentation guide Manual Collection S7-1500/ET 200MP The Manual Collection contains the complete documentation on the SIMATIC S7-1500 automation system and the ET 200MP distributed I/O system gathered together in one file. You can find the Manual Collection on the Internet (https://support.industry.siemens.com/cs/ww/en/view/86140384).
  • Page 9: Product Overview

    Product overview Properties Article number 6ES7522-5FH00-0AB0 View of the module Figure 2-1 View of the DQ 16x230VAC/1A ST module Properties The module has the following technical properties: • 16 digital outputs (Triac) • Rated output voltage 120 V/230 V AC •...
  • Page 10 The following component can be ordered separately: Front connectors, including potential jumpers and cable ties For more information on accessories, refer to the S7-1500, ET 200MP system manual (https://support.industry.siemens.com/cs/ww/en/view/59191792). Digital output module DQ 16x230VAC/1A ST Triac (6ES7522-5FH00-0AB0) Equipment Manual, 12/2021, A5E34934069-AC...
  • Page 11: Functions

    Product overview 2.2 Functions Functions 2.2.1 Switching cycle counter The function records the number of switching cycles of the output and thus the switching cycles of a connected actuator, such as those of solenoid valves. When the specified number of switching cycles is reached, the "Limit value warning" maintenance interrupt is triggered, provided it is configured and enabled.
  • Page 12 Product overview 2.2 Functions Principle of operation The module counts the switching cycles by evaluating the rising edges of an output signal. If the module detects a rising edge, the switching cycle counter (24-bit) for the respective channel is incremented. After an overflow of the switching cycle counter, it starts again with If you activate the "Maintenance switching cycles"...
  • Page 13: Wiring

    This section contains the block diagram of the module and outlines various wiring options. You can find information on wiring the front connector, creating a cable shield, etc. in the Wiring section of the S7-1500, ET 200MP system manual (https://support.industry.siemens.com/cs/ww/en/view/59191792). Note Do not insert the potential jumpers included with the front connector!
  • Page 14: Parameters/Address Space

    Parameters/address space Parameters DQ 16x230VAC/1A ST parameters When you assign the module parameters in STEP 7, you use various parameters to specify the module properties. The following table lists the configurable parameters. The effective range of the configurable parameters depends on the type of configuration. The following configurations are possible: •...
  • Page 15: Declaration Of Parameters

    Parameters/address space 4.2 Declaration of parameters Declaration of parameters Switching cycle counter maintenance You use this parameter to enable the maintenance alarm "Limit value warning" when the switching cycle counter limit is violated. You configure the limit with the parameter "Switching cycle limit" for each channel CHx. Reaction to CPU STOP Determines the reaction of the output to the CPU going into STOP state or when the connection to the CPU is interrupted.
  • Page 16: Address Space

    Parameters/address space 4.3 Address space Address space The module can be configured differently in STEP 7; see following table. Depending on the configuration, additional/different addresses are assigned in the process image output/input. Configuration options of DQ 16x230VAC/1A ST You can configure the module with STEP 7 or with a GSD file. When you configure the module by means of the GSD file, the configurations are available under different short designations/module names.
  • Page 17 Parameters/address space 4.3 Address space Address space for configuration as 16-channel DQ 16x230VAC/1A ST The figure below shows the address space allocation for the configuration as 16-channel module. You can freely assign the start address for the module. The addresses of the channels are derived from the start address.
  • Page 18 Parameters/address space 4.3 Address space Address space for configuration as 1 x 16-channel DQ 16x230VAC/1A ST MSO For the configuration as a 1 x 16-channel module (module-internal Shared Output, MSO), channels 0 to 15 of the module are copied to multiple submodules. Channels 0 to 15 are then available with identical values in various submodules.
  • Page 19 Parameters/address space 4.3 Address space The following figure shows the assignment of the address space for submodules 1 and 2 and the value status. Figure 4-3 Address space for configuration as 1 x 16-channel DQ 16x230VAC/1A ST MSO with value status Digital output module DQ 16x230VAC/1A ST Triac (6ES7522-5FH00-0AB0) Equipment Manual, 12/2021, A5E34934069-AC...
  • Page 20 Reference You can find information on the module-internal shared input/shared output (MSI/MSO) function in the section Module-internal shared input/shared output (MSI/MSO) of the Function Manual PROFINET (https://support.industry.siemens.com/cs/ww/en/view/49948856). Digital output module DQ 16x230VAC/1A ST Triac (6ES7522-5FH00-0AB0) Equipment Manual, 12/2021, A5E34934069-AC...
  • Page 21: Diagnostic Alarms

    Diagnostic alarms Status and error displays LED displays The figure below shows the LED displays (status and error displays) of DQ 16x230VAC/1A ST. Figure 5-1 LED displays of the module DQ 16x230VAC/1A ST Digital output module DQ 16x230VAC/1A ST Triac (6ES7522-5FH00-0AB0) Equipment Manual, 12/2021, A5E34934069-AC...
  • Page 22 Diagnostic alarms 5.1 Status and error displays Meaning of the LED displays The following table explains the meaning of the status and error displays. RUN and ERROR LED Table 5- 1 RUN and ERROR status and error displays Meaning Solution ERROR Voltage missing or too low at backplane bus •...
  • Page 23: Diagnostics Alarms

    Diagnostic alarms 5.2 Diagnostics alarms Diagnostics alarms Diagnostics alarms A diagnostics alarm is generated and the ERROR LED flashes on the module for each diagnostics event. The diagnostics alarms can be read out in the diagnostics buffer of the CPU, for example. You can evaluate the error codes with the user program. Table 5- 3 Diagnostics alarms, their meaning and corrective measures Diagnostics alarm...
  • Page 24: Technical Specifications

    Technical specifications Technical specifications of the DQ 16x230VAC/1A ST The following table shows the technical specifications as of 12/2021. You can find a data sheet including daily updated technical specifications on the Internet (https://support.industry.siemens.com/cs/ww/en/pv/6ES7522-5FH00-0AB0/td?dl=en). Article number 6ES7522-5FH00-0AB0 General information Product type designation...
  • Page 25 Technical specifications Article number 6ES7522-5FH00-0AB0 Digital outputs Type of digital output Triac Number of digital outputs Current-sinking Current-sourcing Digital outputs, parameterizable Short-circuit protection 6.3 A melting fuse, slow-blow • built-in fuse Size of motor starters according to NEMA, max. Switching capacity of the outputs •...
  • Page 26 Technical specifications Article number 6ES7522-5FH00-0AB0 Interrupts/diagnostics/status information Diagnostics function Substitute values connectable Alarms • Diagnostic alarm • Maintenance interrupt Diagnoses • Monitoring the supply voltage • Wire-break • Short-circuit Diagnostics indication LED Yes; green LED • RUN LED Yes; red LED •...
  • Page 27 Technical specifications Power reduction (derating) to aggregate current of outputs (per module) The following graphs show the loading capacity of the outputs in relation to the mounting position of the S71500 automation system/ET 200MP distributed I/O system and the ambient temperature.
  • Page 28: Dimensional Drawing

    Dimensional drawing The dimension drawing of the module on the mounting rail, as well as a dimension drawing with open front cover, are provided in the appendix. Always observe the specified dimensions for installation in cabinets, control rooms, etc. Figure A-1 Dimension drawing of the DQ 16x230VAC/1A ST module Digital output module DQ 16x230VAC/1A ST Triac (6ES7522-5FH00-0AB0) Equipment Manual, 12/2021, A5E34934069-AC...
  • Page 29 Dimensional drawing Figure A-2 Dimension drawing of the DQ 16x230VAC/1A ST module, side view with open front cover Digital output module DQ 16x230VAC/1A ST Triac (6ES7522-5FH00-0AB0) Equipment Manual, 12/2021, A5E34934069-AC...
  • Page 30: Parameter Data Records

    0 and 1. You can find more information in the Interrupts section of the manual for the PROFIBUS DP interface module in the Internet (http://support.automation.siemens.com/WW/view/en/78324181). Digital output module DQ 16x230VAC/1A ST Triac (6ES7522-5FH00-0AB0) Equipment Manual, 12/2021, A5E34934069-AC...
  • Page 31 Parameter data records B.1 Parameter assignment and structure of the parameter data records Assignment of data record and channel For the configuration as a 1 x 16-channel module, the parameters are located in data records 64 to 79 and are assigned as follows: •...
  • Page 32 Parameter data records B.1 Parameter assignment and structure of the parameter data records Structure of data sets 64 to 79 The figure below shows the structure of data set 64 for channel 0 as an example. The structure is identical for channels 1 to 15. The values in byte 0 and byte 1 are fixed and may not be changed.
  • Page 33 Parameter data records B.1 Parameter assignment and structure of the parameter data records Structure of data set 129 You can read the current states of the switching cycle counters with data set 129. The counter status is supplied for each channel in UDINT format. The following figure shows you the structure of data set 129.
  • Page 34 Parameter data records B.1 Parameter assignment and structure of the parameter data records Structure of data set 130 The limits of the switching cycle counters are read out with data set 130. The set value is supplied for each channel in UDINT format. The following figure shows you the structure of data set 130.
  • Page 35 Parameter data records B.1 Parameter assignment and structure of the parameter data records Structure of data set 131 The following figure shows you the structure of data set 131. Enable a parameter by setting the corresponding bit to "1". Figure B-4 Structure of data set 131: Bytes 0 to 7 Digital output module DQ 16x230VAC/1A ST Triac (6ES7522-5FH00-0AB0) Equipment Manual, 12/2021, A5E34934069-AC...