Acoustic Noise Or Vibration; Warnings And Alarms - Danfoss VLT CDS 803 Quick Manual

Compressor drive
Hide thumbs Also See for VLT CDS 803:
Table of Contents

Advertisement

Quick Guide
1
1

1.5 Acoustic Noise or Vibration

If the compressor is making noise or vibrations at certain frequencies, try the following:
Speed bypass, parameter group 4-6* Speed Bypass

1.6 Warnings and Alarms

Fault
Alarm/
number
Warning bit
number
2
4
7
8
9
10
11
13
14
16
17
(parameter 1
18
6-91 Alarm
Word 2)
30
31
32
38
44
47
48
(parameter 1
49
6-91 Alarm
Word 2)
58
22
Fault text
Warning
16
Live zero error
14
Mains ph. loss
11
DC over volt
10
DC under volt
9
Inverter overload
8
Motor ETR over
7
Motor th over
5
Overcurrent
2
Earth Fault
12
Short Circuit
4
Ctrl. word TO
10
Start failed
19
U phase loss
20
V phase loss
21
W phase loss
17
Internal fault
28
Earth Fault
Control Voltage
23
Fault
25
VDD1 supply low
11
AMA internal
Danfoss A/S © 12/2015 All rights reserved.
®
VLT
Compressor Drive CDS 803
Alarm
Trip
Cause of problem
locked
Signal on terminal 53 or 54 is less than 50% of the value set
in parameter 6-10 Terminal 53 Low Voltage,
parameter 6-12 Terminal 53 Low Current,
X
X
parameter 6-20 Terminal 54 Low Voltage, or
parameter 6-22 Terminal 54 Low Current. See also parameter
group 6-0* Analog I/O Mode.
Missing phase on the supply side or too high voltage
X
X
X
imbalance. Check the supply voltage. See
parameter 14-12 Function at Mains Imbalance.
X
X
DC-link voltage exceeds limit.
X
X
DC-link voltage drops below voltage warning low limit.
X
X
More than 100% load for too long.
The motor is too hot due to more than 100% load for too
X
X
long. See parameter 1-90 Motor Thermal Protection.
The thermistor or the thermistor connection is disconnected.
X
X
See parameter 1-90 Motor Thermal Protection.
X
X
X
Inverter peak current limit is exceeded.
X
X
Discharge from output phases to ground.
Short circuit in the compressor or on the compressor
X
X
terminals.
No communication to the frequency converter. See parameter
X
X
group 8-0* General Settings.
The speed has not been able to exceed
X
parameter 1-78 Compressor Start Min Speed [Hz] during start
within the allowed time.
Motor phase U is missing. Check the phase. See
X
X
parameter 4-58 Missing Motor Phase Function.
Motor phase V is missing. Check the phase. See
X
X
parameter 4-58 Missing Motor Phase Function.
Motor phase W is missing. Check the phase. See
X
X
parameter 4-58 Missing Motor Phase Function.
X
X
Contact the local Danfoss supplier.
Discharge from output phases to ground, using the value of
X
X
parameter 15-31 Alarm Log Value if possible.
X
X
X
24 V DC may be overloaded.
X
X
Control voltages low. Contact the local Danfoss supplier
X
The speed is below the specified limit in
parameter 1-87 Compressor Min. Speed for Trip [Hz].
X
X
Contact the local Danfoss supplier.