9
Settings
9.1
Description of Gas 210 ECO PRO parameters
Tab.30
Factory setting for user level parameters
Parame
Description
ter
Flow temperature: T
Post-circulation of the pump
Boiler control
Display screen
Tab.31
Factory setting for installer level parameters
Parame
Description
ter
Maximum fan speed for central
heating
Minimum fan speed for central
heating
Start speed
Maximum central heating flow
temperature
Base point heating curve outside
temperature
Base point heating curve flow
temperature
Climate point heating curve out
side temperature
Outside temperature for frost
protection
Fault relay function (optional)
Minimum water pressure (option
al)
Minimum gas pressure monitor
(optional)
114494 - v.05 - 06022018
Adjustment range
20 to 90ºC
SET
0 to 98 minutes
99 minutes = continuous
0 = CH off
1 = CH on
0 = Simple
1 = Extended
2 = Automatic switching to sim
ple
Adjustment range
G20 (H gas)
(x100 rpm/min)
G20 (H gas)
(x100 rpm/min)
Only modify for flue gas cascade
and when converting to propane
(upon request).
G20 (H gas)
(x100 rpm/min)
Only modify for flue gas cascade
and when converting to propane
(upon request).
20 - 90 °C
0 - 30 °C
(only with outside sensor)
0 - 90 °C
(only with outside sensor)
-30 - 0 °C
(only with outside sensor)
-30 - 0 °C
(only with outside sensor)
-30 - 0 °C
(only with outside sensor)
1 - 60:10 bar (only with water
pressure sensor)
0 = Off
0 = Off
1 = on (only with minimum gas
pressure sensor)
210-80
210-120
210-160
80
80
80
3
3
1
1
2
2
210-80
210-120
210-160
51
64
48
12
13
10
17
17
17
90
90
90
20
20
20
20
20
20
-15
-15
–15
-10
–10
–10
1
1
0
0
0
0
9 Settings
210-200
80
3
3
1
1
2
2
210-200
57
12
17
90
20
20
–15
–10
1
1
0
0
0
0
47