The boiler also comes with a release input that can be used to release/
block the burner. This input can be used in conjunction with flue gas valve
end switches, hydraulic shut-off valves etc., for example. This input can be
X4
X5
found on the RL terminals on the terminal block X6.
Pump
N L
Status
Pump
N
L
N L
AD-4000042
A pump with the following specifications can be connected:
X4
X5
Attach the pump to the Pump terminals on the terminal block X4. By se
lecting a programme at user level, the finishing time for the circulation
Pump
pump can be set to when heat demand has ended.
N L
Status
Pump
N
L
N L
AD-4000045
A PC can be connected to the 'telephone connector' X7 using a serial/
optional serial cable and the corresponding interface. Together with the
Recom software, you can import, alter and export various boiler settings.
See the user instructions that come with this software.
X6
X7
AD-0001421-01
6.5.5
The IF-01 PCB can be built into the instrument box or the housing for the
PCBs. See the instructions provided with the product.
X5
X4
AD-0000054-01
Release input
Connecting the circulation pump
On/off pump with a supply voltage of 230 VAC (50Hz) and 300 VA.
Connecting a PC
Connection options for the 0–10 V PCB (IF-01)
6 Installation