Veeder-Root TLS-350 System Setup Manual page 54

Table of Contents

Advertisement

5
System Setup
LED: Turn on the front panel Warning or write in your new label in the Custom Alarm Label column of Table 5-1.
When you have completed your custom alarm label entries, press the PRINT key while in System Setup, to print
out a copy of your changes.
To continue, press ENTER:
CUSTOM ALARM LABELS
DISABLED
Press CHANGE:
CUSTOM ALARM LABELS
ENABLED
Press ENTER:
ENABLED
PRESS <STEP> TO CONTINUE
Press STEP to continue:
CUSTOM ALARM LABELS
SYSTEM ALARMS : NO
Press CHANGE and ENTER to access available System Alarms, or STEP to move through the alarm sets: In-Tank
alarms, Liquid Sensor alarms, etc. When making changes, standard setup entry procedures apply - you can
designate a single device or all devices for the label change. After each custom label entry, you then select enable
or disable for each of the four console alarm indicators assigned to that custom alarm: LCD, Print, Beep, and LED.
5-20
Custom Alarm Labels