Veeder-Root TLS-350 System Setup Manual page 172

Table of Contents

Advertisement

17
Reconciliation Setup
99: Tank with no probe
00: Remove meter from tank/meter map
xx: Any tank number set up for BIR. (Note: only the primary tank needs to be entered for a manifolded set of
tanks. The primary tank is the tank with the lowest number in the set. If a tank number is entered that is part of a
manifolded set, but it is not the primary tank, the selection will be rejected.)
Press STEP until you see the message:
INDIVIDUAL METER OFFSET
PRESS <ENTER>
Press STEP to return to the Disp. Module Data String menu if DIM is installed or to Automatic Daily Closing menu
if DIM is not installed; or press ENTER to change the meter offset for the selected fuel position/meter. The system
displays:
FUEL
METER TANK OFFSET
XX
XX
XX
Then press CHANGE. The Offset value flashes '0'. Enter the desired offset in increments of ±0.01% with a
mximum range of ±9.99% and Press ENTER to confirm your change. Press STEP to continue to the next meter.
Press FUNCTION to exit the Reconciliation Setup function.
Ticketed Delivery must be enabled to view this menu.
+X.XX
17-6