Output Relay Setup
Press STEP to display the message:
R1: IN-TANK ALARMS
LEAK: NO TANKS
This message shows the first kind of alarm condition for In-Tank Alarms: LEAK. You must tell the system whether to
assign the displayed alarm condition (in this case In-Tank Leak Alarms) to the selected relay for No Tanks, All
Tanks, or Single Tanks. To choose No Tanks, press STEP. (The system displays the next In-Tank Alarm condition:
HIGH WATER.)
To choose All Tanks, press CHANGE once. Press ENTER to confirm your choice. The system displays:
LEAK: ALL TANKS
PRESS <STEP> TO CONTINUE
Press STEP to specify the assignment method for the next In-Tank Alarm condition (HIGH WATER).
To choose Single Tanks, press CHANGE twice in response to the LEAK: NO TANKS message. Press ENTER to
confirm your choice. The system displays:
LEAK: SINGLE TANK
PRESS <STEP> TO CONTINUE
Press STEP to display the message: The system displays:
R1: (Name)
T1 LEAK: NO
Use the above message to specify the tank number(s) that you want to assign to the relay. If you do not want to
assign the tank number shown (T1, T2, etc.), press TANK/SENSOR until you see the tank number that you want
to assign to the relay. When the correct tank number appears, press CHANGE and press ENTER. The system
confirms your entry (for T1) with the message:
R1: T1 LEAK: YES
PRESS <TANK> TO CONTINUE
Continue to press TANK/SENSOR to select additional tanks. For example, pressing TANK once would display the
following message:
R1: (Name)
T2 LEAK: NO
Repeat the steps described above to assign additional tanks to the relay. When you have assigned all the tanks
you want to the relay, press STEP. The system displays the assignment method message for the next In-Tank Alarm
condition:
R1: IN-TANK ALARMS
HIGH WATER: NO TANKS
Repeat the procedures described for the LEAK alarm condition until you have specified an assignment method for
the all remaining In-Tank Alarm conditions (ref. Alarm List in Section 6, Table 6-2).
Press TANK/SENSOR to select additional tanks for the In-Tank Leak alarm. When you have specified all tanks for
the first In-Tank alarm, press STEP to advance to the next alarm group. Repeat the steps described above to
assign tanks for each In-Tank alarm. After you have specified tanks for each In-Tank alarm condition, press STEP to
advance to the next alarm group.