7-6. Step-4 Trial run of BACnet

Connect the building management system and carry out a trial run.
Step-4
① Set to "ONLINE" from the
®
BACnet
Setting Tool.
Setting PC
② Disconnect the HUB
and Setting PC.
AE-200/AE-50/EW-50
(1) ONLINE setting
A setting is made to "ONLINE" from the BACnet
(approximately 10 minutes for maximum time required)
When AE-200/AE-50/EW-50 restarts, a group device with no remote controller may stop.
When a valid "BACnet connection" license is not registered, the setting will not change to "ONLINE".
(2) Removal of Setting PC
Remove the LAN cable from the Setting PC.
®
(3) BACnet
connection
Connect the LAN2 port of AE-200/AE-50/EW-50 and BACnet
(4) Trial run item and trial run method
Refer to the following pages for trial run items and trial run methods.
Note that an air conditioning unit and building management system are required for the trial run.
WT07919X04
®
③ Connect LAN2 to the
BACnet
HUB
HUB
LAN2
LAN1
M-NET
AE-200/
Outdoor
AE-50/EW-50
unit
Outdoor
Other
unit

function

®
HUB.
Building management system
HUB
®
BACnet
M-NET
Indoor unit
ME remote controller
M-NET
Indoor unit
ME remote controller
®
Setting Tool. AE-200/AE-50/EW-50 restarts automatically.
®
using a LAN cable.
42