Mitsubishi Electric AE-200A Instruction Book page 51

Air conditioning control system, bacnet function
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

Object
Night Purge State
Thermo On Off State
External Heat Source
State
Trend Log Room Temp
*16
Trend Log Group
Apportioned Electric
Energy
*12 *14 *16
Trend Log Interlocked
Units Apportioned Electric
Energy
*12 *14 *16
Trend Log PIcontroller
Electric Energy 1–4
*12
*14 *16
WT07919X04
Object ID
INACTIVE(0): OFF
BI_01xx46
ACTIVE(1): ON
INACTIVE(0): Thermo
BI_01xx47
ACTIVE(1): Thermo ON
INACTIVE(0): OFF
BI_01xx50
ACTIVE(1): ON
LOG_01xx80
LOG_01xx83
LOG_61aa83
LOG_41mm84~87
Status
(1) Using AE-200/AE-50/EW-50 or the remote
controller, run Night Purge for LOSSNAY of
a specific group.
(2) In the building management system, check
to see that the status of Night Purge of the
relevant group has been updated to "ON".
(3) Using AE-200/AE-50/EW-50 or the remote
controller, stop Night Purge for LOSSNAY
of a specific group.
(4) In the building management system, check
to see that the status of Night Purge of the
relevant group has been updated to "OFF".
(1) Using AE-200/AE-50/EW-50 or the remote
controller, have a specific group perform fan
operation.
(2) In the building management system, check
to see that the thermo ON/OFF status of
the relevant group has been updated to
"Thermo OFF".
(3) Using AE-200/AE-50/EW-50 or the remote
controller, cool a specific group using a low
OFF
temperature setting of at least 2°C lower
than the room temperature or heat at a high
temperature setting of at least 2°C higher
than the room temperature.
(4) In the building management system, check
to see that the thermo ON/OFF status of
the relevant group has been updated to
"Thermo ON".
(1) Change the ON/OFF conditions of the
external heat source that is connected to
the indoor unit CN24 of the specific group.
(2) In the building management system, check
to see that the state of External heat source
for the relevant group is updated to the
changed value.
(1) Record the "Room Temp" value and check
the log record of the "LogBuffer" property
and check that the "Room Temp" data has
been logged in after the time longer than
collection cycle that is set from the building
management system has been elapsed.
(1) Record the "Group Apportioned Electric
Energy" value and check the log record of
the "LogBuffer" property and check that the
"Group Apportioned Electric Energy" data
has been logged in after the time longer
than collection cycle that is set from the
building management system has been
elapsed.
(1) Record the "Interlocked Units Apportioned
Electric Energy" value and check the
log record of the "LogBuffer" property
and check that the "Interlocked Units
Apportioned Electric Energy" data has
been logged in after the time longer than
collection cycle that is set from the building
management system has been elapsed.
(1) Record the "PIcontroller Electric Energy
1–4" value and check the log record of the
"LogBuffer" property and check that the
"PIcontroller Electric Energy 1–4" data has
been logged in after the time longer than
collection cycle that is set from the building
management system has been elapsed.
51
Checking procedures