Mitsubishi Electric AE-200A Instruction Book page 45

Air conditioning control system, bacnet function
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

Object
Set Temp Heat
*8
Set Temp Auto
*8
Set High Limit Setback
Temp
*5
Set Low Limit Setback
Temp
*5
WT07919X04
Object ID
ºF/ºC
AV_01xx25
(32ºF–199ºF/0.0ºC–
99.0ºC)
ºF/ºC
AV_01xx26
(32ºF–199ºF/0.0ºC–
99.0ºC)
ºF/ºC
AV_01xx27
(32ºF–199ºF/0.0ºC–
99.0ºC)
ºF/ºC
AV_01xx28
(32ºF–199ºF/0.0ºC–
99.0ºC)
Status
(1) From the building management system, set
the heating set temperature for a specific
group.
(2) Using AE-200/AE-50/EW-50 or the remote
controller, check to see that the heating
set temperature for the relevant group has
been updated to an operating value.
(3) Using AE-200/AE-50/EW-50 or the
*7
remote controller, change the heating set
temperature for a specific group.
(4) In the building management system, check
to see that the heating set temperature for
the relevant group has been updated to the
operating value.
(1) From the building management system, set
the set temperature (single-set-point in the
Auto mode) for a specific group.
(2) Using AE-200/AE-50/EW-50 or the remote
controller, check to see that the set
temperature (single-set-point in the Auto
mode) for the relevant group has been
updated to an operating value.
(3) Using AE-200/AE-50/EW-50 or the remote
controller, change the set temperature
*7
(single-set-point in the Auto mode) for a
specific group.
(4) In the building management system, check
to see that the set temperature (single-set-
point in the Auto mode) for the relevant
group has been updated to the operating
value.
(1) From the building management system,
set the set temperature (upper limit in the
Setback mode) for a specific group.
(2) Using AE-200/AE-50/EW-50 or the remote
controller, check to see that the set
temperature (upper limit in the Setback
mode) for the relevant group has been
updated to an operating value.
(3) Using AE-200/AE-50/EW-50 or the remote
*7
controller, change the set temperature
(upper limit in the Setback mode) for a
specific group.
(4) In the building management system, check
to see that the set temperature (upper limit
in the Setback mode) for the relevant group
has been updated to the operating value.
(1) From the building management system,
set the set temperature (lower limit in the
Setback mode) for a specific group.
(2) Using AE-200/AE-50/EW-50 or the
remote controller, check to see that the
set temperature (lower limit in the Setback
mode) for the relevant group has been
updated to an operating value.
(3) Using AE-200/AE-50/EW-50 or the remote
*7
controller, change the set temperature
(lower limit in the Setback mode) for a
specific group.
(4) In the building management system, check
to see that the set temperature (lower limit
in the Setback mode) for the relevant group
has been updated to the operating value.
45