Mitsubishi Electric AE-200A Instruction Book page 52

Air conditioning control system, bacnet function
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

Object
Trend Log Pulse Input
Electric Energy 1–4
*12
*14 *16
Trend Log Group
Apportionment Parameter
*12 *15 *16
Trend Log Interlocked
Units Apportionment
Parameter
*12 *15 *16
* xx: Group number (01–50)
* mm: PI controller address (01–50)
* aa: Interlocked unit address (01–50)
*1 Do not use this when "External Input Setting" for AE-200/AE-50/EW-50 is set to "ON/OFF (Level signal)". "External Input Setting" can
be configured on the Initial Setting Tool, Web Browser for Initial Settings, or AE-200/AE-50's LCD. (Refer to the AE-200/AE-50/EW-50
Instruction Book (Initial Settings) for settings methods.)
*2 The air conditioning unit error code (4 digits) is output to the Description and the Message Text of event notification. When an error
occurs, check to see that it coincides with the error code (4 digits) detected by AE-200/AE-50/EW-50 or the remote controller.
*3 When the M-NET transmission line has been removed, units in a group with no remote controller stop.
*4 "Dry" can be used only when the "Use Dry Mode" setting is enabled (checked) on the BACnet
disabled (unchecked).)
*5 It can only be used if the system controller is AE-200A/AE-50A/EW-50A and the indoor unit is a Setback mode supported model.
*6 "Mid 1" and "Mid 2" can be used only when the "Use Fan Speed Mid1/Mid2" setting is enabled (checked) on the BACnet
default setting is disabled (unchecked).)
*7 Accuracy and value ranges in BACnet
model of the connected air conditioning units and remote controllers.
*8 The objects that can be used for the temperature setting differ depending on the model and the setting. Refer to section 5-3 "Set
temperature objects" for details.
*9 For details of the setting method, refer to the item in "External Input Setting" in the AE-200/AE-50/EW-50 Instruction Book (Initial
Settings).
*10 The error code (4 digits) is output to the Description and the Message Text of event notification. When an error occurs, check to see that
it coincides with the error code (4 digits) detected by AE-200/AE-50/EW-50.
*11 Outputs the PI controller error code (4 digits) to the Description and EVENT Notification Message Text. Check that when an error occurs,
this matches the error code (4 digits) detected with the AE-200/AE-50/EW-50.
*12 When "Charge" license is not registered, the correct value is not stored.
*13 Results until XX:00 and XX:30 minutes every hour are reflected at XX:15 and XX:45 respectively.
*14 Can be used only if there is a metering device.
*15 Can be used only when there is no metering device.
*16 The initial value of the log interval of the trend log is 1 minute (Room Temp) or 30 minutes (other than Room Temp). To change the log
interval, it is necessary to write (WriteProperty) in the "Log_Interval" property from BACnet
*17 When the display temperature of the building management system is updated by COV notification, the difference of a maximum of
[COV_Increment setting value + 0.1]ºC can be generated between the temperatures displayed on the building management system and
on the AE-200/AE-50/EW-50. If the difference of the display temperature is within this value, assume that there is no difference.
WT07919X04
Object ID
LOG_410084~87
LOG_01xx88
LOG_61aa88
®
. Accuracy and value ranges that can be actually set or measured will differ depending on the
Status
(1) Record the "Pulse Input Electric Energy
1–4" value and check the log record of the
"LogBuffer" property and check that the
"Pulse Input Electric Energy 1–4" data has
been logged in after the time longer than
collection cycle that is set from the building
management system has been elapsed.
(1) Record the "Group Apportionment
parameter" value and check the log record
of the "LogBuffer" property and check that
the "Group Apportionment parameter" data
has been logged in after the time longer
than collection cycle that is set from the
building management system has been
elapsed.
(1) Record the "Interlocked Units Apportionment
Parameter" value and check the log record
of the "LogBuffer" property and check
that the "Interlocked Units Apportionment
Parameter" data has been logged in after
the time longer than collection cycle that is
set from the building management system
has been elapsed.
®
Trial Run Tool before trial run.
52
Checking procedures
®
Setting Tool. (The default setting is
®