5-8. BACnet

information and storage timing/cycle in nonvolatile memory
within the AE-200/AE-50/EW-50
The following BACnet
AE-200/AE-50/EW-50 for each storage timing or cycle in the table below.
After the property value has been updated, if the power source for AE-200/AE-50/EW-50 is cut within the storage
cycle and when restart is carried out, it may return to the property value before updating.
On Off State
Thermo On Off State
External Heat Source State
Room Temp
Group Apportioned Electric Energy
Interlocked Units Apportioned Electric Energy
PIcontroller Electric Energy 1–4
Pulse Input Electric Energy 1–4
Group Apportionment Parameter
Interlocked Units Apportionment Parameter
Trend Log Room Temp
Trend Log Group Apportioned Electric Energy
Trend Log Interlocked Units Apportioned Electric Energy
Trend Log PIcontroller Electric Energy 1–4
Trend Log Pulse Input Electric Energy 1–4
Trend Log Group Apportionment Parameter
Trend Log Interlocked Units Apportionment Parameter
Device
Notification Class
*1 At XX:05 minutes every hour
*2 At XX:15 minutes and XX:45 minutes every hour
*3 Will be saved within 1 minute after the property value is updated.
WT07919X04
®
information (object property value) is stored in nonvolatile memory inside
Object
Object ID
BI_01xx02
BI_01xx47
Present_Value
BI_01xx50
High_Limit
Low_Limit
AI_01xx09
Deadband
Limit_Enable
Present_Value
Value_Change_
Time
AC_01xx39
Value_Before_
AC_61aa39
Change
AC_41mm40–43
Value_Set
AC_410040–43
AC_01xx44
Pulse_Rate
AC_61aa44
High_Limit
Low_Limit
Limit_Enable
Enable
Start_Time
LOG_01xx80
Stop_Time
Log_Interval
Enable
Start_Time
LOG_01xx83
Stop_Time
LOG_61aa83
LOG_41mm84–87
Log_Interval
LOG_410084–87
Record_Count
LOG_01xx88
Total_Record_
LOG_61aa88
Count
Log_Buffer
Active_COV_
DEV_xxxxxx
Subscriptions
CLS_xxxxxx
Recipient_List
33
Storage timing or
Property
cycle
60 minutes
When updated
When updated
When updated
When updated
30 minutes
When updated
When updated
When updated
30 minutes
When updated
When updated
When updated
When updated
When updated
When updated
When updated
When updated
When updated
When updated
When updated
When updated
When updated
When updated
When updated
When updated
*1
*3
*3
*3
*3
*2
*3
*3
*3
*2
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3