Mitsubishi Electric AE-200A Instruction Book page 44

Air conditioning control system, bacnet function
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

Object
Operational Mode State
Fan Speed Setup
Fan Speed State
Room Temp
[Water Temp]
Set Temp
[Set Water Temp]
*8
Set Temp Cool
*8
WT07919X04
Object ID
01: Cool
02: Heat
03: Fan
MI_01xx06
04: Auto
05: Dry
06: Setback
01: Low
02: High
MO_01xx07
03: Mid 2
04: Mid 1
05: Auto
01: Low
02: High
MI_01xx08
03: Mid 2
04: Mid 1
05: Auto
ºF/ºC
AI_01xx09
(32ºF–199ºF/0.0ºC–
99.0ºC)
ºF/ºC
AV_01xx10
(32ºF–199ºF/0.0ºC–
99.0ºC)
ºF/ºC
AV_01xx24
(32ºF–199ºF/0.0ºC–
99.0ºC)
Status
(1) Using AE-200/AE-50/EW-50 or the remote
controller, change the operational mode for
a specific group.
(2) In the building management system, check
to see that the operational mode for the
*4
relevant group has been updated to the
*5
operating mode.
(1) From the building management system,
change the fan speed for a specific group.
(2) Using AE-200/AE-50/EW-50 or the remote
*6
controller, check to see that the fan speed
*6
for the relevant group is updated to the
operating fan speed.
(1) Using AE-200/AE-50/EW-50 or the remote
controller, change the fan speed for a
specific group.
*6
(2) In the building management system, check
*6
to see that the fan speed for the relevant
group is updated to the operating fan
speed.
(1) Change the intake air temperature for a
specific group by cooling or heating.
(2) Check to see that the display on the
building management system coincides with
*7
the display on the AE-200/AE-50/EW-50 or
the remote controller.
(1) From the building management system, set
the set temperature for a specific group.
(2) Using AE-200/AE-50/EW-50 or the
remote controller, check to see that the
set temperature for the relevant group has
been updated to an operating value.
(3) Using AE-200/AE-50/EW-50 or the remote
*7
controller, change the set temperature for a
specific group.
(4) In the building management system, check
to see that the set temperature for the
relevant group has been updated to the
operating value.
(1) From the building management system, set
the cooling set temperature for a specific
group.
(2) Using AE-200/AE-50/EW-50 or the remote
controller, check to see that the cooling
set temperature for the relevant group has
been updated to an operating value.
(3) Using AE-200/AE-50/EW-50 or the
*7
remote controller, change the cooling set
temperature for a specific group.
(4) In the building management system, check
to see that the cooling set temperature for
the relevant group has been updated to the
operating value.
44