Mitsubishi Electric AE-200A Instruction Book page 47

Air conditioning control system, bacnet function
Hide thumbs Also See for AE-200A:
Table of Contents

Advertisement

Object
System Forced Off
(individual)
System Forced Off
(collective)
Air Direction Setup
Air Direction State
Ventilation Mode Setup
Ventilation Mode State
Air To Water Mode Setup
WT07919X04
Object ID
INACTIVE(0): Reset
BV_01xx21
ACTIVE(1): Execute
INACTIVE(0): Reset
BV_019921
ACTIVE(1): Execute
01: Horizontal
02: Downblow 60%
MO_01xx22
03: Downblow 80%
04: Downblow 100%
05: Swing
01: Horizontal
02: Downblow 60%
MI_01xx23
03: Downblow 80%
04: Downblow 100%
05: Swing
01: Heat Recovery
MO_01xx35
02: Bypass
03: Auto
01: Heat Recovery
MI_01xx36
02: Bypass
03: Auto
01: Heating
02: Heating ECO
MO_01xx37
03: Hot Water
04: Anti-freeze
05: Cooling
Status
(1) Set "External Input Setting" of the
AE-200/AE-50/EW-50 to "Demand
(Level signal)/Not in use"
emergency stop for a specific group from
the building management system.
(2) In the building management system, check
to see that the air conditioning units of the
relevant group are stopped. Also, check
to see that run/stop operations have been
prohibited by the remote controller in the
relevant group.
(3) From the building management system,
carry out emergency stop release for a
specific group.
(4) Check to see that run/stop operations have
been permitted by the remote controller in
the relevant group.
(1) Set "External Input Setting" of the
AE-200/AE-50/EW-50 to "Demand
(Level signal)/Not in use"
batch emergency stop from the building
management system.
(2) In the building management system, check
to see that all air conditioning units have
been stopped. Also, check to see that run/
stop operations have been prohibited by all
remote controllers.
(3) From the building management system,
carry out batch emergency stop release.
(4) Check to see that run/stop operations have
been permitted by all remote controllers.
(1) From the building management system,
change the air direction for a specific group.
(2) Using AE-200/AE-50/EW-50 or the remote
controller, check to see that the air direction
for the relevant group is updated to the
operating air direction.
(1) Using AE-200/AE-50/EW-50 or the remote
controller, change the air direction for a
specific group.
(2) In the building management system, check
to see that the air direction for the relevant
group is updated to the operating air
direction.
(1) From the building management system,
change the ventilation mode for a specific
group.
(2) Using AE-200/AE-50/EW-50 or the remote
controller, check to see that the ventilation
mode for the relevant group is updated to
the operating mode.
(1) Using AE-200/AE-50/EW-50 or the remote
controller, change the ventilation mode for a
specific group.
(2) In the building management system, check
to see that the ventilation mode for the
relevant group is updated to the operating
mode.
(1) From the building management system,
change the Air To Water mode for a specific
group.
(2) Using AE-200/AE-50/EW-50 or the remote
controller, check to see that the Air To Water
mode for the relevant group is updated to
the operating mode.
47
Checking procedures
*9
and operate
*9
and carry out