Parameters
3.15 Main Menu - Application Functions -
Group 22
3.15.1 22-0* Miscellaneous
Parameter group for extra settings.
3
3
22-01 Power Filter Time
Range:
0.50 s
[0.02 - 10 s] Set the time constant for the filtered
*
3.15.2 22-2* No-Flow Detection
Illustration 3.16 No-flow Detection
The frequency converter includes functions for detecting if the load conditions in the system allow the motor to be
stopped:
Low power detection.
One of these 2 signals must be active for a set time (parameter 22-24 No-Flow Delay) before selected action takes place.
Possible actions to select (parameter 22-23 No-Flow Function):
No action
Warning
Alarm
Sleep mode
86
TR150 and TR170
Function:
power readout. A higher value gives a
more steady readout but a slower system
response to changes.
02/2017 All rights reserved.
22-02 Sleepmode CL Control Mode
Option:
Function:
[0]
Normal
The feedback is detected. Some parameters are
*
checked.
[1]
Simplified The feedback is not detected. Only sleep speed
and time are checked.
This parameter is for sleep mode running in process
closed-loop mode. Use this parameter to configure
whether to detect the feedback for sleep mode.