Parameters

3.3 Main Menu - Brakes - Group 2

3.3.1 2-0* DC Brakes
Parameters for configuring the DC brake and DC hold
functions.
2-00 DC Hold/Motor Preheat Current
Range:
Function:
NOTICE
50 %
[0 -
160 %]
*
MOTOR OVERHEATING
The maximum value depends on the rated
motor current.
To avoid motor damage caused by
overheating, do not run at 100% for too
long.
Set holding current as a percentage of the rated
motor current I
M,N
Current. Parameter 2-00 DC Hold/Motor Preheat
Current holds the motor function (holding torque)
or pre-heats the motor. This parameter is active if
DC hold is selected in parameter 1-72 Start
Function [0] DC Hold/delay time or
parameter 1-80 Function at Stop [1] DC hold/Motor
Preheat.
2-01 DC Brake Current
Range:
Function:
NOTICE
50
[0 -
%
150 %
*
MOTOR OVERHEATING
]
The maximum value depends on the rated
motor current.
To avoid motor damage caused by
overheating, do not run at 100% for too
long.
Set current as % of rated motor current,
parameter 1-24 Motor Current. When speed is
below the limit set in parameter 2-04 DC Brake Cut
In Speed, or when the DC-brake inverse function is
active (in parameter group 5-1* Digital Inputs set to
[5] DC-brake inverse; or via the serial port), a DC-
brake current is applied on a stop command. See
parameter 2-02 DC Braking Time for duration.
2-02 DC Braking Time
Range:
Function:
10 s
[0 - 60 s] Set the duration of the DC-brake current set in
*
parameter 2-01 DC Brake Current, once
activated.
BAS-SVP16B-EN
Programming Guide
in parameter 1-24 Motor
02/2017 All rights reserved.
2-04 DC Brake Cut In Speed
Range:
Function:
0 Hz
[ 0 - 400
This parameter is for setting the DC-brake
*
Hz]
cut-in speed at which parameter 2-01 DC
Brake Current is to be active with a stop
command.
2-06 Parking Current
Range:
Function:
100
[0 -
Set current as percentage of rated motor
%
150 %]
current, parameter 1-24 Motor Current. Active
*
with parameter 1-73 Flying Start. The parking
current is active during the time period set in
parameter 2-07 Parking Time.
NOTICE
Parameter 2-06 Parking Current is only
active when 1 of the PM motor
construction options is selected in
parameter 1-10 Motor Construction.
2-07 Parking Time
Range:
Function:
3 s
[0.1 - 60
Set the duration of the parking current time set
*
s]
in parameter 2-06 Parking Current. Active with
parameter 1-73 Flying Start.
NOTICE
Parameter 2-07 Parking Time is only active
when options of parameter 1-10 Motor
Construction are set to enable PM motors.
3.3.2 2-1* Brake Energy Function
Parameter group for selecting dynamic brake parameters.
2-10 Brake Function
Option:
Function:
[0]
Off
The brake resistor is not active.
*
[2]
AC brake
AC brake is active.
2-16 AC Brake, Max current
Range:
Function:
100 %
[0 - 160 %] Enter the maximum permissible current
*
when using the AC brake to avoid
overheating motor windings.