Trane TR150 Programming Manual page 57

Hide thumbs Also See for TR150:
Table of Contents

Advertisement

Parameters
6-12 Terminal 53 Low Current
Range:
4 mA
[0 - 20
*
mA]
3
3
6-13 Terminal 53 High Current
Range:
20 mA
[0 - 20
*
mA]
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
0
[-4999 -
*
4999 ]
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Size
related
4999 ]
*
6-16 Terminal 53 Filter Time Constant
Range:
0.01 s
[0.01 - 10
*
s]
6-19 Terminal 53 mode
Option:
[0]
Current mode
[1]
Voltage mode
*
3.7.3 6-2* Analog Input 54
Parameters for configuring the scaling and limits for analog
input 54 (terminal 54).
56
Function:
Enter the low current value. This reference
signal corresponds to the low reference/
feedback value that is set in
parameter 6-14 Terminal 53 Low Ref./Feedb.
Value. To activate parameter 6-01 Live Zero
Timeout Function, set the value to >2 mA.
Function:
Enter the high current value corresponding
to the high reference/feedback set in
parameter 6-15 Terminal 53 High Ref./Feedb.
Value.
Function:
Enter the reference or feedback value that
corresponds to the voltage or current set in
parameter 6-10 Terminal 53 Low Voltage to
parameter 6-12 Terminal 53 Low Current.
Function:
[-4999 -
Enter the reference or feedback value
that corresponds to the voltage or
current set in parameter 6-11 Terminal
53 High Voltage to
parameter 6-13 Terminal 53 High
Current.
Function:
Enter the time constant. This constant is a
first-order digital low-pass filter time
constant for suppressing electrical noise in
terminal 53. A high time constant value
improves dampening, but also increases the
time delay through the filter.
Function:
Select whether terminal 53 is used for
current or voltage input.
TR150 and TR170
6-20 Terminal 54 Low Voltage
Range:
0.07 V
*
6-21 Terminal 54 High Voltage
Range:
10 V
*
6-22 Terminal 54 Low Current
Range:
4 mA
*
6-23 Terminal 54 High Current
Range:
20 mA
*
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
0
[-4999 -
*
4999 ]
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Size
related
*
6-26 Terminal 54 Filter Time Constant
Range:
0.01 s
*
02/2017 All rights reserved.
Function:
[0 - 10
Enter the voltage (V) that corresponds to the
V]
low reference value (set in
parameter 6-24 Terminal 54 Low Ref./Feedb.
Value). To activate parameter 6-01 Live Zero
Timeout Function, set the value at >1 V.
Function:
[0 - 10 V] Enter the voltage (V) that corresponds to the
high reference value (set in
parameter 6-25 Terminal 54 High Ref./Feedb.
Value).
Function:
[0 - 20
Enter the low current value. This reference
mA]
signal corresponds to the low reference/
feedback value set in parameter 6-24 Terminal
54 Low Ref./Feedb. Value. To activate the live
zero timeout function in parameter 6-01 Live
Zero Timeout Function, set the value to >2 mA.
Function:
[0 - 20
Enter the high current value corresponding
mA]
to the high reference/feedback value set in
parameter 6-25 Terminal 54 High Ref./Feedb.
Value.
Function:
Enter the reference or feedback value that
corresponds to the voltage or current set in
parameter 6-21 Terminal 54 High Voltage/
parameter 6-22 Terminal 54 Low Current.
Function:
[-4999 -
Enter the reference or feedback value
4999 ]
that corresponds to the voltage or
current set in parameter 6-21 Terminal
54 High Voltage/
parameter 6-23 Terminal 54 High
Current.
Function:
[0.01 - 10
Enter the time constant, which is a first-
s]
order digital low-pass filter time constant
for suppressing electrical noise in terminal
54. A high time constant value improves
BAS-SVP16B-EN