Parameters

3.12 Main Menu - Data Readouts - Group 16

3.12.1 16-0* General Status
16-00 Control Word
Range:
Function:
0
[0 - 65535 ] View the control word sent from the frequency
*
converter via the serial communication port in
hex code.
Bit Bit = 0
00 Preset reference option lsb
01 Preset reference option 2
nd
preset references
02 DC brake
03 Coasting
04 Quick stop
05 Freeze output
06 Ramp stop
07 No function
08 No function
09 Ramp 1
10 Data not valid
11 Relay_A not active
12 Relay_B not active
13 Choice of set-up lsb
14 No function
15 No function
Table 3.6 Control Word
16-01 Reference [Unit]
Range:
0 ReferenceFeed-
[-4999 - 4999
backUnit
ReferenceFeed-
*
backUnit]
16-02 Reference [%]
Range:
Function:
0 %
[-200 - 200 %] View the total reference. The total
*
reference is the sum of digital, analog,
preset, bus, and freeze references.
16-03 Status Word
Range:
Function:
0
[0 - 65535 ] View the status word sent from the frequency
*
converter via the serial communication port in
hex code.
BAS-SVP16B-EN
Programming Guide
Bit = 1
bit of
Ramp
Enable
Ramp
Ramp
Start
Reset
Jog
Ramp 2
Valid
Relay_A activated
Relay_B activated
No function
Reversing
Function:
View the present reference
value applied on impulse
or analog basis in the unit
resulting from the configu-
ration selected in
parameter 1-00 Configu-
ration Mode (Hz).
02/2017 All rights reserved.
Bit Bit = 0
00 Control not ready
01 Drive not ready
02 Coasting
03 No fault
04 No warning
05 Reserved
06 No trip lock
07 No warning
08 Speed ≠ ref.
09 Local control
10 Out of range
11 Not running
12 No function
13 Voltage OK
14 Current OK
15 Thermal-level OK
Table 3.7 Status Word
16-05 Main Actual Value [%]
Range:
Function:
0 %
[-200 - 200 %] View the 2 byte word sent with the status
*
word to the bus master reporting the
main actual value.
16-09 Custom Readout
Range:
0 CustomRea-
[0 - 9999
doutUnit
CustomRea-
*
doutUnit]
3.12.2 16-1* Motor Status
16-10 Power [kW]
Range:
Function:
0 kW
[0 - 1000
Displays the actual motor power in kW.
*
kW]
The value shown is calculated on the basis
of the actual motor voltage and motor
current.
16-11 Power [hp]
Range:
Function:
0 hp
[0 - 1000
View the actual motor power in hp. The
*
hp]
value shown is calculated based on the
actual motor voltage and motor current.
Bit = 1
Ready
Ready
Enable
Trip
Warning
Trip lock
Warning
Speed = ref.
Bus control
Frequency OK
Running
No function
Above limit
Above limit
Above limit
Function:
View the user-defined readouts
as defined in
parameter 0-30 Custom Readout
Unit, parameter 0-31 Custom
Readout Min Value, and
parameter 0-32 Custom Readout
Max Value.
79
3
3