Extended Status Words; List Of Warnings And Alarms - Trane TR150 Programming Manual

Hide thumbs Also See for TR150:
Table of Contents

Advertisement

Troubleshooting

4.4 Extended Status Words

Bit
Hex
Dec
0
1
1
1
2
2
2
4
4
3
8
8
4
10
16
5
20
32
6
40
64
7
80
128
8
100
256
9
200
512
10
400
1024
11
800
2048
12
1000
4096
13
2000
8192
14
4000
16384
15
8000
32768
16
10000
65536
17
20000
131072
18
40000
262144
19
80000
524288
20
100000
1048576
21
200000
2097152
22
400000
4194304
23
800000
8388608
24
1000000
16777216
25
2000000
33554432
26
4000000
67108864
27
8000000
134217728
28
10000000
268435456
29
20000000
536870912
30
40000000
1073741824
31
80000000
2147483648
Table 4.3 Extended Status Words
BAS-SVP16B-EN
Programming Guide
Parameter 16
Parameter 16-95
-94 Ext.
Ext. Status
Status Word
Word 2
Ramping
Off
AMA running
Hand/Auto
Start CW/CCW
0
0
0
0
0
Feedback
0
high
Feedback low
0
Output
Control Ready
current high
Output
Drive Ready
current low
Output
frequency
Quick Stop
high
Output
DC Brake
frequency low
0
Stop
0
0
Freeze Output
Braking
Request
0
Freeze Output
OVC active
Jog Request
AC brake
Jog
0
Start request
0
Start
Reference
0
high
Reference low
Start Delay
0
Sleep
0
Sleep boost
0
Running
0
Bypass
0
Fire Mode
0
External Interlock
Firemodelimi-
0
texceed
0
FlyStart Active
0
0
0
0
Database
0
busy
02/2017 All rights reserved.

4.5 List of Warnings and Alarms

WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures
recommended in this section of the manual could result
in exposure to electrical, mechanical, or other potential
safety hazards. Always refer to the safety warnings
provided throughout this manual concerning these
procedures. Unless specified otherwise, disconnect all
electrical power including remote disconnect and
discharge all energy storing devices such as capacitors
before servicing. Follow proper lockout/tagout
procedures to ensure the power cannot be inadvertently
energised. When it is necessary to work with live
electrical components, have a qualified licensed
electrician or other individual who has been trained in
handling live electrical components perform these tasks.
Failure to follow all of the recommended safety warnings
provided, could result in death or serious injury.
WARNING/ALARM 2, Live zero error
This warning or alarm only appears if parameter 6-01 Live
Zero Timeout Function is configured. The signal on 1 of the
analog inputs is less than 50% of the minimum value
programmed for that input. This condition can be caused
by broken wiring or a faulty device sending the signal.
WARNING/ALARM 3, No motor
No motor is connected to the output of the frequency
converter. Check the cable connection between the
frequency converter and the motor.
WARNING/ALARM 4, Mains phase loss
A phase is missing on the supply side, or the mains
voltage imbalance is too high. This message also appears
for a fault in the input rectifier on the frequency converter.
Options are programmed at parameter 14-12 Function at
Mains Imbalance.
CAUTION
Live Electrical Components!
Troubleshooting
Check the supply voltage and supply currents to
the frequency converter.
WARNING/ALARM 7, DC overvoltage
If the DC-link voltage exceeds the limit, the frequency
converter trips after a time.
Troubleshooting
Extend the ramp time.
Activate functions in parameter 2-10 Brake
Function.
Activate overvoltage control in
parameter 2-17 Over-voltage Control.
4
4