3.8 Main Menu - Communications and
Options - Group 8
3.8.1 8-0* General Settings
3
3
8-01 Control Site
Option:
[0]
Digital and
*
ctrl.word
[1]
Digital only
[2]
Controlword
only
8-02 Control Source
Option:
[0]
None
[1]
FC Port
*
8-03 Control Timeout Time
Range:
Size
[0.1 -
related
6500 s]
*
8-04 Control Timeout Function
Option:
[0]
Off
*
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[20] N2 Override
Release
60
Function:
This parameter overrules settings in
parameter 8-50 Coasting Select to
parameter 8-56 Preset Reference Select.
Control by using both digital input and
control word.
Control by using digital inputs only.
Control by using control word only.
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
Select the source of the control word.
Function:
Enter the maximum time expected to pass
between the reception of 2 consecutive
telegrams. If this time is exceeded, it
indicates that the serial communication has
stopped. The function selected in
parameter 8-04 Control Timeout Function is
carried out.
Function:
Select the timeout function. The timeout
function is activated when the control
word fails to be updated within the time
period specified in parameter 8-03 Control
Timeout Time.
This option is valid only when the protocol
is N2.
TR150 and TR170
3.8.2 8-3* Drive
8-30 Protocol
Option:
[0]
FC
*
[2]
Modbus
RTU
[3]
Metasys
N2
[4]
FLN
[5]
BACNet
8-31 Address
Range:
Size
related
*
8-32 Baud Rate
Option:
[0] 2400 Baud
[1] 4800 Baud
[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
[5] 57600 Baud
[6] 76800 Baud
[7] 115200 Baud
8-33 Parity / Stop Bits
Option:
[0] Even Parity, 1 Stop
Bit
02/2017 All rights reserved.
Function:
Select the protocol for the integrated RS485
port.
Communication according to the Drive
Protocol.
Communication according to the Modbus RTU
protocol.
Communication protocol. The N2 software
protocol is designed to be general in nature to
accommodate the unique properties each
device may have.
Communication according to the FLN protocol.
Communication according to the BACNet
protocol.
Function:
[ 0.0 -
Enter the address for the RS485 port.
247 ]
Valid range: 1–126 for FC-bus OR 1–
247 for Modbus.
Function:
Select the baud rate for the RS485 port
Default refers to the FC protocol. Changing the
protocol in parameter 8-30 Protocol may
change the baud rate.
Changing protocol in parameter 8-30 Protocol
may change the baud rate.
Default setting for FLN.
Default setting for:
BACnet.
Metasys N2.
Default setting for Modbus RTU.
Function:
Parity and stop bits for the protocol
using the FC port. For some of the
protocols, not all options are available.
Default refers to the FC protocol.
Changing protocol in parameter 8-30
Protocol may change the baud rate.
BAS-SVP16B-EN