3.1 Main Menu - Operation and Display -
Group 0
Parameters related to the fundamental functions of the
frequency converter, function of the keypad keys, and
configuration of the keypad display.
3.1.1 0-0* Basic Settings
0-01 Language
Option:
Function:
Defines the language to be used in the
display.
[0]
English
*
[1]
Deutsch
[2]
Francais
[3]
Dansk
[4]
Spanish
[5]
Italiano
[28]
Bras.port
[255] Numeric prg.
0-03 Regional Settings
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
To meet the needs for different default settings
in different parts of the world,
parameter 0-03 Regional Settings is implemented
in the frequency converter. The selected setting
influences the default setting of the motor
nominal frequency.
[0]
Interna-
Sets the default value of parameter 1-23 Motor
*
tional
Frequency to 50 Hz.
[1]
North
Sets the default value of parameter 1-23 Motor
America
Frequency to 60 Hz.
BAS-SVP16B-EN
Programming Guide
0-04 Operating State at Power-up
Option:
[0]
Resume
*
[1]
Forced
stop,
ref=old
0-06 GridType
Option:
[0]
200-240V/50Hz/IT-grid
[1]
200-240V/50Hz/Delta
[2]
200-240V/50Hz
[10]
380-440V/50Hz/IT-grid
[11]
380-440V/50Hz/Delta
[12]
380-440V/50Hz
[20]
440-480V/50Hz/IT-grid
[21]
440-480V/50Hz/Delta
[22]
440-480V/50Hz
[30]
525-600V/50Hz/IT-grid
[31]
525-600V/50Hz/Delta
[32]
525-600V/50Hz
[100] 200-240V/60Hz/IT-grid
[101] 200-240V/60Hz/Delta
02/2017 All rights reserved.
Function:
Select the operating mode after reconnection of
the frequency converter to mains voltage after
power-down when operating in Hand (local)
mode.
Resumes operation of the frequency converter,
maintaining the same local reference and the
same start/stop condition (applied by [Hand
On]/[Off] on the keypad or local start via a
digital input as before the frequency converter
was powered down.
Uses saved reference [1] to stop the frequency
converter, but at the same time retains the local
speed reference in memory before powering
down. After mains voltage is reconnected, and
after receiving a start command (pressing [Hand
On] key or using the local start command via a
digital input), the frequency converter restarts
and operates at the retained speed reference.
Function:
Select the grid type of the supply
voltage/frequency.
NOTICE
Not all options are supported
in all power sizes.
IT Grid is a supply mains, where
there are no connections to
ground.
Delta is a supply mains where the
secondary part of the transformer
is delta connected and 1 phase is
connected to ground.
3
3
25